Fault Messages
975-0307-01-01
5–7
F500
Serial Number
Failure, Service
Required.
No
The silicon serial ID number
has failed and the XW Auto
Generator Start has gone into
Standby.
Call your dealer or
Xantrex.
F501
Memory Failure.
Service
Required.
No
The XW Auto Generator Start
has suffered a non-volatile
memory failure.
Call your dealer or
Xantrex.
F505
Internal Failure.
Service
Required.
No
A controller fault has occurred
and the XW Auto Generator
Start has gone into Standby.
Clear the fault. If the fault
persists, call your dealer
or Xantrex.
Table 5-2
XW Auto Generator Start Fault Messages
Fault
Number
Message
Self-
clearing?
Cause
Action