SPC
I Co
mmand T
ree
975-0200
-01-01
A-25
A
Setup the
Current
control source
for Non-
Isolated APG.
[:]SYSTem[<channel>]:REMote:SOURce
:CURRent[:NISOlated]
Alter or query the state of
the remote programming
non isolated current APG
source.
?|LOCal|AVOLtage
|ARESistive
Yes
Set Front
Panel lock
state.
[:]SYSTem[<channel>]:REMote:STATe
Change front panel control
mode
?|LOCal|REMote
Yes
Query SCPI
Version
[:]SYSTem[<channel>]:VERSion?
Returns the SCPI version
to which the instrument
complies. Format is
YYYY.V
Yes
SCPI Help
[:]SYSTem[<channel>]:HELP[:HEADers]?
Query system for all
supported SCPI command
headers.
Yes
Legacy Help
[:]SYSTem[<channel>]:HELP:LEGacy?
Query the system for all
supported Xantrex legacy
commands.
Yes
Command
Syntax Help
[:]SYSTem[<channel>]:HELP:SYNTax?
Query the system for the
syntax of a command. The
command should be input
after the query as a string
parameter. To enter a
command you should do
this by typing the
command as you would on
the command line without
parameters. To find all
command headers see
[:]SYSTem:HELP
[:HEADERS]?
<COMMAND>
Yes
Table A-9
System Commands (Continued)
Содержание XTR 100-17
Страница 2: ......
Страница 3: ...XTR 850 Watt and 1700 Watt Series Programmable DC Power Supply Operating Manual...
Страница 6: ......
Страница 18: ...xvi...
Страница 48: ...2 18...
Страница 86: ...Local Operation 3 38 975 0200 01 01 Figure 3 4 Split Supply Operation V V Common Power Supply Power Supply Load...
Страница 122: ...4 30...
Страница 208: ...6 20...
Страница 244: ...A 36...
Страница 250: ...B 6...
Страница 264: ...C 14...
Страница 272: ...IX 4...
Страница 273: ......