Power Supply Operation
TM-XDOP-01XN
3–47
To set the current limits:
Step # Do This
You Will See
1
ERROR MSGS
2
until you see the “SETPT LIMIT”
option
SETPT LIMIT
3
Voltage Limit
4
Current Limit
5
High 0A
6
Use the Current knob, arrow keys, or
numeric keypad to enter a value. The value
must be within 0A to 103% of the unit’s
rated current and must be higher than the
current setpoint.
High #####A
7
Low 0A
The Maximum setting is
saved and the Minimum
setting appears.
8
Use the Voltage knob, arrow keys, or
numeric keypad to enter a value. The value
must be within 0A to 103% of the unit’s
rated current and must be lower than the
current setpoint.
Low #####A
9
The setting is saved and
the display returns to its
default operating mode.
MENU
ENTER
ENTER
ENTER
ENTER
TM-XDOP-01XN.book Page 47 Monday, July 17, 2006 11:19 AM
Содержание XDC 10-1200
Страница 2: ......
Страница 3: ...XDC 6000 Watt and 12000 Watt Series Digital Programmable Power Supply Operating Manual ...
Страница 8: ...vi ...
Страница 12: ...x ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 39: ...2 Installation Chapter 2 explains how to mount and wire the XDC and also how to perform basic functional tests ...
Страница 43: ...Location Mounting and Ventilation TM XDOP 01XN 2 5 Figure 2 2 Unpacking the Power Supply 6000 Watt shown ...
Страница 48: ...Installation 2 10 TM XDOP 01XN Figure 2 5 Attaching the AC Input Wires for 6000 Watt units ...
Страница 59: ...Load Connections TM XDOP 01XN 2 21 Figure 2 9 Output for 12000 Watt units low and medium voltage ...
Страница 61: ...Load Connections TM XDOP 01XN 2 23 Figure 2 11 Output for 12000 Watt units high voltage 300 600V ...
Страница 114: ...Operation 3 52 TM XDOP 01XN ...
Страница 208: ...A 16 ...
Страница 224: ...B 16 ...
Страница 259: ...D Error Messages Appendix D lists all the error codes and their meanings ...
Страница 268: ...D 10 ...
Страница 269: ...E GPIB Appendix E describes the General Purpose Interface Bus GPIB commands and lines supported by this model ...
Страница 283: ......