Remote Operation
4–54
TM-XDOP-01XN
TEMPerature Sub-Register
This shows whether the temperature of critical components is near or over the
maximum operating temperature.
Standard Event Status Register
The standard event status register sets bits for specific events during power supply
operation. All bits in the standard event status registers are set through the error
event queue. The register is defined by 488.2 and is controlled using 488.2
common commands, *ESE, *ESE?, and *ESR?.
Figure 4-6, “IEEE 488.2 Status Register and Status Byte” on page 4–54
summarizes the standard Event Status Register.
Table 4-19
TEMPerature Sub-Register
Bit
Bit Weight
Bit Name
Description
0
1
Over TEMperature
Set if the power supply temperature exceeds the maximum
operating temperature.
1
2
High TEMperature
Set if the power supply temperature exceeds 90% of the
maximum operating temperature.
Figure 4-6
IEEE 488.2 Status Register and Status Byte
Not Used
Not Used
Not Used
MAV
Standard Event Status Register
1
0
3
2
5
4
7
6
Summary of QUESTionable Status
RQS/MSS
Summary of OPERation Status
1
0
3
2
5
4
7
6
9
8
11
10
13
12
15
14
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
+
Operation Complete
Query Error
Device Dependent Error
User Request
Power On
Execution Error
Command Error
Not Used
TM-XDOP-01XN.book Page 54 Monday, July 17, 2006 11:19 AM
Содержание XDC 10-1200
Страница 2: ......
Страница 3: ...XDC 6000 Watt and 12000 Watt Series Digital Programmable Power Supply Operating Manual ...
Страница 8: ...vi ...
Страница 12: ...x ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 39: ...2 Installation Chapter 2 explains how to mount and wire the XDC and also how to perform basic functional tests ...
Страница 43: ...Location Mounting and Ventilation TM XDOP 01XN 2 5 Figure 2 2 Unpacking the Power Supply 6000 Watt shown ...
Страница 48: ...Installation 2 10 TM XDOP 01XN Figure 2 5 Attaching the AC Input Wires for 6000 Watt units ...
Страница 59: ...Load Connections TM XDOP 01XN 2 21 Figure 2 9 Output for 12000 Watt units low and medium voltage ...
Страница 61: ...Load Connections TM XDOP 01XN 2 23 Figure 2 11 Output for 12000 Watt units high voltage 300 600V ...
Страница 114: ...Operation 3 52 TM XDOP 01XN ...
Страница 208: ...A 16 ...
Страница 224: ...B 16 ...
Страница 259: ...D Error Messages Appendix D lists all the error codes and their meanings ...
Страница 268: ...D 10 ...
Страница 269: ...E GPIB Appendix E describes the General Purpose Interface Bus GPIB commands and lines supported by this model ...
Страница 283: ......