Specifications
A–4
975-0402-01-01
This guide for use by qualified installers only
Float voltage:
±0.1 V for 12 V units
±0.2 V for 24 V units
12 V units
24 V units
25 °C (77 °F)
25 °C (77 °F)
Flooded 13.5
27.0
GEL 13.8
27.6
AGM 13.4
26.8
Lead-calcium
13.5
27.0
Equalize mode current
50% rated output ±6%
Equalize mode—
maximum output
voltage
12 V units:16 ±0.1 Vdc
24 V units:32 ±0.2 Vdc
Off-state current draw
(without remote
installed)
12 V units: <30 mA
24 V units: <20 mA