Electrical Diagrams and Schematics
152315 Rev C
2–5
utility-side neutral does not affect the operation of the inverter, however
connection of the neutral on the inverter-side does affect the operation and must
be left floating or disconnected. Single-phase, grounded loads which may be
present between the transformer and utility, will maintain their existing ground
reference at the utility distribution transformer.
Electrical Diagrams and Schematics
Since installations vary widely, a sample electrical diagram of the PV100S is
provided in Figure A-1 on page A–3. This diagram is to be used for system
planning purposes only.
For more detailed information, refer to the schematic illustrations for
model-specific electrical schematics.
Model PV100S-480:
•
Figure A-2, “PV100S-480 Schematic for Main Power
Distribution (152316 E1)” on page A–4
•
Figure A-3, “PV100S-480 Schematic for Control Power
Distribution (152316 E2)” on page A–5
•
Figure A-4, “PV100S-480 Schematic for Converter Control
Unit (152316 E3)” on page A–6
Model PV100S-208:
•
Figure A-5, “PV100S-208 Schematic Main Power Distribution (152376 C1)”
on page A–7
•
Figure A-6, “PV100S-208 Schematic for Control Power
Distribution (152376 C2)” on page A–8
•
Figure A-7, “PV100S-208 Schematic for Converter Control
Unit (152376 C3)” on page A–9
CAUTION: Equipment Damage
If the Isolation Transformer (T6-X0) neutral terminal is tied to ground, it will cause
irreparable damage to the PV100S. Check local regulations for their requirements
regarding the connection of these neutrals.
WARNING: Lethal Voltage
Grounding the neutral of a Wye-wound transformer may create an “open delta” condition,
depending on the utility configuration. This condition may keep the PV100S from
detecting a loss of phase condition on the utility system, which may allow potentially
lethal voltage to be present on the open-phase wiring.
Содержание PV100S-480
Страница 1: ...PV100S 100 kW Grid Tied Photovoltaic Inverter PV100S 208 PV100S 480 Planning and Installation Manual...
Страница 2: ......
Страница 3: ...PV100S 100 kW Grid Tied Photovoltaic Inverter Planning and Installation Manual...
Страница 8: ...vi...
Страница 14: ...xii...
Страница 18: ...xvi...
Страница 77: ...A Schematics Appendix A contains useful schematics to aid with installation...
Страница 78: ...Schematics A 2 152315 Rev C This page intentionally left blank...
Страница 79: ...Appendix A Schematics 152315 Rev C A 3 Figure A 1 Electrical Diagram sample...
Страница 80: ...Schematics Appendix A A 4 152315 Rev C Figure A 2 PV100S 480 Schematic for Main Power Distribution 152316 E1...
Страница 81: ...Appendix A Schematics 152315 Rev C A 5 Figure A 3 PV100S 480 Schematic for Control Power Distribution 152316 E2...
Страница 82: ...Schematics Appendix A A 6 152315 Rev C Figure A 4 PV100S 480 Schematic for Converter Control Unit 152316 E3...
Страница 83: ...Appendix A Schematics 152315 Rev C A 7 Figure A 5 PV100S 208 Schematic Main Power Distribution 152376 C1...
Страница 84: ...Schematics Appendix A A 8 152315 Rev C Figure A 6 PV100S 208 Schematic for Control Power Distribution 152376 C2...
Страница 85: ...Appendix A Schematics 152315 Rev C A 9 Figure A 7 PV100S 208 Schematic for Converter Control Unit 152376 C3...
Страница 86: ...Schematics Appendix A A 10 152315 Rev C This page was intentionally left blank...
Страница 89: ......