Operation
Auto Sequencing
64
Operating Manual for Multichannel Functionality (GPIB-M)
Operation
To run, stop or pause a sequence, use the following command:
PROGram:STATe [RUN|PAUSe|STOP]
•
Once the programmed sequence has been selected, you can start it by setting the
state to RUN, by sending the command
PROG:STAT RUN
.
•
At any time you can pause the sequence by sending
PROG:STAT PAUS
.
A paused sequence will cause the supply to hold the output levels at the setpoints
programmed by the current step. To resume, set the state to RUN again.
•
To end the sequence operation, send the command
PROG:STAT STOP
.
Sending RUN will restart the auto sequence program from the first step.
•
You can query the state of the selected auto sequence program with
PROG:STAT?
Trigger
If the auto sequence was programmed to wait for a trigger, the power supply holds
the output levels at the programmed setpoints until a trigger is received. It then
advances to the next step. A trigger must come from the selected trigger source,
which may be the GPIB bus, a SCPI command or the user lines.
Skipping a Step
To advance the sequence to the next step, send the command:
PROGram:STEP:NEXT
Querying Operation
You can query the step number that is currently operating:
PROGram:STEP:EXEC?
You can also query the number of times the sequence has executed:
PROGram:REP:EXEC?
Exiting Auto Sequence Operation
To exit auto sequence operation and return to normal operation, send the command:
PROGram:EXIT
Содержание GPIB-M-HPD
Страница 2: ......
Страница 18: ...List of Figures xvi Operating Manual for Multichannel Functionality GPIB M...
Страница 26: ...Features and Specifications Specifications 24 Operating Manual for Multichannel Functionality GPIB M...
Страница 94: ...Current Sharing Operation 92 Operating Manual for Multichannel Functionality GPIB M...
Страница 98: ...GPIB Performance Specifications 96 Operating Manual for Multichannel Functionality GPIB M...
Страница 118: ...SCPI Command Reference Expressions 116 Operating Manual for Multichannel Functionality GPIB M...
Страница 132: ...Calibration Restore Factory Calibration 130 Operating Manual for Multichannel Functionality GPIB M...
Страница 133: ......