Basic Installation Procedures
975-0767-01-01
39
AC wiring must be sized appropriately using conductors with
insulation rated at least 75 °C to carry full load current on the input
and output AC circuits in accordance with the electrical codes or
regulations applicable to your installation.
is based on the
U.S. National Electrical Code and the Canadian Electrical Code,
assuming two-conductor-plus-ground cable, using 75 °C wiring, at
an ambient temperature of 30 °C. Other codes and regulations
may be applicable to your installation.
Required Breaker
Size (A)
Required Wire
Size (AWG)
Freedom X
1200
30 A maximum
15 A maximum through
a GFCI
10 AWG
Table 8 Required AC wire size vs. required breaker rating
When making the AC input and AC output connections, observe the
correct color code for the appropriate AC wire, as described in
below.
Color
AC Wire
Black/Red/Brown
Line
White/light blue
Neutral
Table 9 Color codes for typical AC wiring
Color
AC Wire
Green, green/yellow, or bare
copper
Ground
NOTICE
REVERSE POLARITY DAMAGE
Make sure the wires are connected properly. Improper connections
(connecting a line conductor to a neutral conductor, for example)
will cause the Freedom X 1200 to malfunction and may
permanently damage the inverter. Damage caused by a reverse
polarity connection is not covered by your warranty.
Failure to follow these instructions can result in equipment
damage.
Wiring Knockouts
When installing wires to the AC terminals, the AC input and output
holes are provided to accommodate ½" trade-size strain relief
clamps
a
.
a
Compatible strain-relief clamp with manufacturer part number: 3302-TB.