WTI RSM-8R4-1 Скачать руководство пользователя страница 151

16-1

16. Upgrading RSM-8R Firmware

When new, improved versions of the RSM-8R firmware become available, either the 
Firmware Upgrade Utility (recommended) or the "Upgrade Firmware" function (Text 
Interface only) can be used to update the unit.  The following Section describes the 
procedure for updating the RSM-8R unit using the Firmware Upgrade Utility or the 
Upgrade Firmware function.

16.1. Firmware Upgrade Utility (Recommended)

The preferred method for updating RSM-8R units is via the WTI Firmware Upgrade 
Utility.  The WTI Firmware Upgrade Utility allows you to manage firmware updates for 
multiple WTI units from a single interface.  

A zip file that contains the installation files and other documentation for the WTI 
Firmware Upgrade Utility can be downloaded from WTI's FTP server, located at:

ftp://wtiftp.wti.com/pub/TechSupport/Firmware/Upgrade_Utility/

Please refer to the documentation included in the zip file for further instructions.

16.2. The Upgrade Firmware Function (Alternate Method)

The Upgrade Firmware function provides an alternative method for updating the  
RSM-8R firmware.  Updates can be uploaded via FTP or SFTP protocols.

Notes:

•  The FTP/SFTP servers can only be started via the Text Interface.
•  All other ports will remain active during the firmware upgrade procedure.
•  If the upgrade includes new parameters or features not included in the 

previous firmware version, these new parameters will be set to their default 
values.

•  The upgrade procedure will require approximately 15 minutes.

1.  Obtain the update file.  Firmware modifications can either be mailed to the 

customer, or downloaded from WTI.  Place the upgrade CDR in your disk drive or 
copy the file to your hard drive.

2.  Access Text Interface command mode via Serial Port, Telnet or SSH client session, 

using a username/password and port that permit Administrator level commands.

Содержание RSM-8R4-1

Страница 1: ...WTI Part No 13851 Rev J RSM 8R Series RemoteSiteManagerwithPowerControl User s Guide...

Страница 2: ...ue to uneven loading Input Supply Check nameplate ratings to assure there is no overloading of supply circuits that could have an effect on overcurrent protection and supply wiring Grounding Reliable...

Страница 3: ...Before attempting to service or remove this unit please make certain to disconnect the power supply cable from the power source Two Power Supply Cables Note that RSM 8R8 1 and RSM 8R8 2 units feature...

Страница 4: ...ponsible for compliance could void the user s authority to operate the equipment EMC Safety and R TTE Directive Compliance The CE mark is affixed to this product to confirm compliance with the followi...

Страница 5: ...Devices to the RSM 8R Serial Ports 4 2 5 Basic Configuration 5 1 5 1 Communicating with the RSM 8R Unit 5 1 5 1 1 The Text Interface 5 1 5 1 2 The Web Browser Interface 5 2 5 1 3 Access Via PDA 5 3 5...

Страница 6: ...g LDAP Groups 5 50 5 9 8 4 Deleting LDAP Groups 5 50 5 9 9 TACACS Parameters 5 51 5 9 10 RADIUS Parameters 5 53 5 9 10 1 Dictionary Support for RADIUS 5 54 5 9 11 Email Messaging Parameters 5 56 5 10...

Страница 7: ...eral Plugs Text Interface 9 5 9 3 Connecting and Disconnecting Serial Ports Text Interface 9 6 9 3 1 Any to Any Mode 9 6 9 3 1 1 Connecting Ports 9 6 9 3 1 2 Disconnecting Ports 9 8 9 3 1 3 Defining H...

Страница 8: ...rs to a File 15 1 15 2 Restoring Saved Parameters 15 2 15 3 Restoring Previously Saved Parameters 15 3 16 Upgrading RSM 8R Firmware 16 1 16 1 Firmware Upgrade Utility Recommended 16 1 16 2 The Upgrade...

Страница 9: ...Cables Apx 2 B 3 DX9F DTE RJ Snap Adapter Interface Apx 3 B 4 Connecting DB 9M DTE Devices to an RJ 45 Serial Port on an RSM 8R Apx 3 B 5 DX25M DTE RJ Snap Adapter Interface Apx 4 B 6 Connecting DB 2...

Страница 10: ...r access to configuration menus The RSM 8R includes full Radius LDAP and TACACS capability DHCP and an invalid access lockout feature An Audit Log records all user access login and logout times and co...

Страница 11: ...o 240 VAC 15 Amp 12 Amps RSM 8R8 1 8 2 ea 100 to 132 VAC 20 Amp 16 Amps RSM 8R8 2 8 2 ea 200 to 240 VAC 20 Amp 16 Amps In accordance with UL requirements for branch circuits this value has been de rat...

Страница 12: ...owing components CLEAR Button Restarts the RSM 8R4 as described in Section 2 6 Power On Indicator An LED Indicator which lights when AC Power is applied to the unit SET Button Switches all plugs Off o...

Страница 13: ...devices to the serial ports please refer to Section 4 5 and Appendix B For a description of the serial port interface please refer to Appendix A 1 Power On Off Switch Network Port An RJ45 Ethernet po...

Страница 14: ...ion of the serial port interface please refer to Appendix A 1 Activity Indicators A series of LEDs which light to indicate data activity at the corresponding RSM 8R8 Serial Port RESET Button Restarts...

Страница 15: ...own Secondary Power Inlet An IEC320 C20 AC inlet which supplies secondary fallback power to the RSM 8R8 s control functions and switched power outlets Note that the RSM 8R8 includes two power inlets i...

Страница 16: ...o indicate data activity at the RSM 8R4 DCM Serial Ports Serial Ports For connection to console ports on target devices Standard RJ45 connectors configured as DCE ports For more information on connect...

Страница 17: ...tlets RSM 8R4 2 Four 4 each IEC320 C13 Outlets 2 6 Front Panel Button Functions The front panel buttons can be used to perform several functions described below Notes Front Panel button functions can...

Страница 18: ...ble below for information concerning power requirements and maximum load Note that RSM 8R8 series units feature two power inlets Model No Total Outlets Input Voltage Input Feed Max Load RSM 8R4 1 4 10...

Страница 19: ...hough these parameters can be easily redefined for this Quick Start procedure it is recommended to configure your communications program to accept the default parameters The RSM 8R features a default...

Страница 20: ...previously accessed command mode via the Web Browser Interface exit command mode log out then re enter command mode using the Text Interface as described in Section 3 3 Proceed as follows to connect...

Страница 21: ...successfully completed b Switch Outlet Off At the command prompt type OFF 1 and then press Enter The status indicator for Plug 1 should go Off indicating that the command has been successfully complet...

Страница 22: ...he instrument nameplate If you are not sure of the type of power service available please contact your local power company Reliable earthing grounding of this unit must be maintained Particular attent...

Страница 23: ...can also be used to allow local users to configure and control the RSM 8R unit Ports 1 is designated as a Set Up Port and accordingly cannot be reconfigured as a buffer mode or passive mode port in or...

Страница 24: ...e the Text Interface to contact the unit via Local PC or SSH connection when setting up the unit for the first time After you have accessed command mode using the Text Interface you can then enable We...

Страница 25: ...e number for the phone line that you have connected to the RSM 8R s internal modem port 2 Login Password Prompt A message will be displayed which prompts you to enter a username login name and passwor...

Страница 26: ...r access via PDA first consult your IT department for appropriate settings Access the RSM 8R command mode via the Text Interface or Web Browser interface as described in this section then configure th...

Страница 27: ...parameters click on the Change Parameters button at the bottom of the menu or the Set button next to the field The following sections describe options and parameters that can be accessed via each of...

Страница 28: ...The User Directory option does not appear in the Web Browser Interface s System Parameters menu and is instead accessed via the Users link on the left hand side of the menu Site ID A text field genera...

Страница 29: ...ing caused by Load Shedding Load Shedding Recovery Ping No Answer Reboots and Scheduled Reboots The Alarm Log will create a record of each instance where an Alarm is triggered or cleared at the RSM 8R...

Страница 30: ...s item can be used to redefine the command prompt that will be displayed when the unit is accessed via the Text Interface The command prompt can be set to either TSM or RSM Default RSM Energywise Conf...

Страница 31: ...ange NTP parameters To cause RSM 8R to immediately contact the NTP server at any time make certain that the NTP feature is enabled and configured then type F and press Enter When the System Parameters...

Страница 32: ...er which the RSM 8R will automatically reactivate the port or protocol or you can issue the UL command type UL and press Enter via the Text Interface to instantly unlock all RSM 8R logical network por...

Страница 33: ...nection to the RSM 8R for the defined SSH Lockout Duration period Default 120 Seconds Telnet Protection Enables Disables and configures the Invalid Access function for Telnet connections When this ite...

Страница 34: ...d attempts that must occur during the length of time specified by the Web Lockout Duration period in order to trigger the Invalid Access Lockout feature for Web access For example if the Web Hit Count...

Страница 35: ...alarm the name of the Alarm triggered a description of the Alarm and the time and date that the Alarm was cleared Temperature Log The Temperature Log provides a record of temperature levels over time...

Страница 36: ...Logs menu and then proceed as follows Audit Log At the Display Logs menu key in the number for the Audit Log option and then press Enter When the Audit Log menu appears key in the number for the Erase...

Страница 37: ...On Callback Without Password Prompt Callbacks will be performed for user accounts that include a Callback Number and the login prompt will not be displayed when the user s modem answers If the account...

Страница 38: ...llback Security you must then define a callback phone number for each desired user account as described in Section 5 5 in order for this feature to function properly When using the On Callback With Pa...

Страница 39: ...rs are allowed to invoke all serial port connection and power switching commands and view all status screens SuperUsers can view configuration menus but are not allowed to change configuration paramet...

Страница 40: ...rts but are limited to the ports specified by the account 5 4 3 Granting Plug Access Each account can be granted access to a different selection of switched power outlets plugs and plug groups When ac...

Страница 41: ...n to save parameters in the Text Interface press the Esc key several times until the RSM 8R displays the Saving Configuration message and the cursor returns to the command prompt 5 5 1 Viewing User Ac...

Страница 42: ...ewOnly accounts are not allowed to invoke switching and reboot commands Plug Group Access Determines which Plug Groups this account will be allowed to control Plug Groups allow you to define a selecti...

Страница 43: ...u have finished selecting or editing account parameters make certain to save the new account information before proceeding In the Web Browser Interface click on the Add User button to save parameters...

Страница 44: ...inistrator Level commands Notes Deleted accounts cannot be automatically restored The RSM 8R allows you to delete the default super account which is included to permit initial access to command mode B...

Страница 45: ...s without addressing each plug individually Given the example above you could quickly reboot all plugs for Department A by either including the Dept_A Plug Group name in a BOOT command line via the Te...

Страница 46: ...rs in the Text Interface press the Esc key several times until the RSM 8R displays the Saving Configuration message and the cursor returns to the command prompt 5 6 3 Modifying Plug Groups The Modify...

Страница 47: ...er and cannot include non printable characters spaces asterisks colons the plus symbol or quotation marks Boot Seq Delay When more than one plug is switched On or a reboot cycle is initiated the Boot...

Страница 48: ...using an account that has User level command access then the Default command will only be applied to the plugs allowed by your account The Default command is not available to ViewOnly level accounts...

Страница 49: ...nd re define plug parameters to ensure that they are switched on in the desired order Notes No two plugs can be assigned the same Boot Priority number When a higher Boot Priority is assigned to any gi...

Страница 50: ...changed to Priority 2 This means that Plug 3 will continue to be switched on first after a reboot but now Plug 4 will be switched on second Plug 1 will be third and Plug 2 will be fourth Once again no...

Страница 51: ...is available to all ports except the Internal Modem Port and is the default Port Mode for Port 1 Passive Mode Allows communication between connected ports but does not allow access to command mode Pa...

Страница 52: ...Baud Rate Any standard rate from 300 bps to 115 2K bps Defaults Serial Ports 1 to 8 9600 bps Internal Modem Port 57 6K bps Bits Parity Default 8 None Stop Bits Default 1 Handshake Mode XON XOFF RTS CT...

Страница 53: ...aks received at the port will be passed to any port that this port is connected to When disabled breaks will be refused at this port Default On Port Mode Parameters Port Name Allows you to assign a na...

Страница 54: ...meters will not be changed until after you exit command mode and disconnect Buffer Mode Parameters When the Buffer Mode is selected the following mode specific parameters may be defined Date Time Stam...

Страница 55: ...cribed in Section 10 3 2 In the default state this feature is disabled no break character is sent when a Raw Socket connection is terminated Note If On Password is selected and Administrator level com...

Страница 56: ...two additional items used to set the priority of Syslog messages generated by this port Facility The facility under which this port will log messages Default Local_0 Level The severity or priority of...

Страница 57: ...he following command line options are available a Copy to All Ports Type CP Enter b Copy to a Range of Ports Type CP m n Enter Where m and n are port numbers that specify the desired range For example...

Страница 58: ...hen configuring the unit via Web or Telnet make certain your DHCP server is set up to assign a known fixed IP address in order to simplify reconnection to the unit after the new address has been assig...

Страница 59: ...r where L is the selected Logoff Character Inactivity Timeout Enables and selects the Inactivity Timeout period for the Network Port If enabled and the port does not receive or transmit data for the s...

Страница 60: ...ddress You will need this new IP address in order to reestablish a network connection with the RSM 8R Telnet Access Enables disables Telnet access When Telnet Access is Off users will not be allowed t...

Страница 61: ...the Web Access parameter is accessed via the Text Interface the resulting submenu will also allow you to select SSL encryption parameters as described in Section 14 Harden Web Security When the Harden...

Страница 62: ...first make certain that this option is enabled for both the serial port and the password account then access command mode via the Text Interface at a free serial port At the RSM prompt invoke the TEL...

Страница 63: ...ber for modem pooling On No Password Uses port number 3300 On Password Uses port number 3100 Note that when the password is enabled you will be prompted to enter a valid RSM 8R username and password I...

Страница 64: ...net mask pairs are allowed these lists can indicate specific addresses or a range of addresses to be allowed or denied When the IP Security feature is properly enabled and a client attempts to connec...

Страница 65: ...on Menu type 5 Enter to display the IP Security Menu b Web Browser Interface Place the cursor over the Network Configuration link on the left hand side of the screen When the fly out menu appears clic...

Страница 66: ...IP addresses will be allowed to connect conversely if ALL is included in the Deny list all IP Addresses will be denied except for IP addresses listed in the Allow list For example if the Deny list in...

Страница 67: ...ach time that the unit powers up or reboots In the Text Interface the Static Route menu is accessed via the Network Configuration menu In the Web Browser Interface the Static Route menu is accessed vi...

Страница 68: ...e Read Only Mode which controls the ability to access configuration functions and invoke switching commands When Enabled you will not be able to change configuration parameters or invoke other command...

Страница 69: ...MP Version is set to V3 Default Public Read Write Community Note that this parameter is not available when the SNMP Version is set to V3 Default Public 5 9 7 SNMP Trap Parameters These menus are used...

Страница 70: ...he LDAP Parameters menu is accessed via the Network Configuration menu In the Web Browser Interface the LDAP Parameters menu is accessed via the flyout menus under the Network Configuration link Notes...

Страница 71: ...en be granted as specified in the default LDAP group Default Off Kerberos Setup Kerberos is a network authentication protocol which provides a secure means of identity verification for users who are c...

Страница 72: ...9 is the internal modem port Plug Access This item is used to determine which plugs members of this group will be allowed to control Default All Plugs Off Plug Group Access This item is used to determ...

Страница 73: ...s used for the Add LDAP Group menu as discussed in Section 5 9 8 1 Note After you have finished modifying LDAP Group parameters make certain to save the changes before proceeding In the Web Browser In...

Страница 74: ...ts own internal username directory This parameter offers three options Off Fallback Local is disabled Default On All Failures Fallback Local is enabled and the unit will fallback to it s own internal...

Страница 75: ...mation on Plug Groups please refer to Section 5 6 Defaults Administrator and SuperUser All Plug Groups On User All Plug Groups Off ViewOnly All Plug Groups Off Notes In order to use this feature Plug...

Страница 76: ...o authenticate the password by checking its own internal username directory This parameter offers three options Off Fallback Local is disabled Default On All Failures Fallback Local is enabled and the...

Страница 77: ...g arguments 0 ViewOnly 1 User 2 SuperUser 3 Administrator For example in order to set command access level to SuperUser the command line would be WTI Super 2 WTI Port Access Determines which port s th...

Страница 78: ...plug group 0 Off Deny Access 1 On Allow Access For example to allow access to the first three defined plug groups out of a total of six defined plug groups the command line would be WTI Group Access...

Страница 79: ...ort number that will be used for email connections Default 25 Domain The domain name for your email server Default undefined Note In order to use domain names you must first define Domain Name Server...

Страница 80: ...ven after you have changed parameters and saved them Notes The RSM 8R will automatically backup saved parameters once a day shortly after Midnight This configuration backup file will contain only the...

Страница 81: ...mmand Scheduled Reboot A scheduled reboot is used to initiate a reboot cycle at a user selected time and day of the week When properly configured and enabled the RSM 8R will reboot one or more outlets...

Страница 82: ...n Name The IP address or Domain Name for the device that you wish to Ping When the device at this address fails to respond to the Ping command the RSM 8R will reboot the selected outlets Default undef...

Страница 83: ...Single Alarm Reboot Default Continuous Alarm Reboot Plug Access Determines which outlet s will be rebooted when this IP address for this Ping No Answer operation does not respond to a Ping command No...

Страница 84: ...Modify Ping No Answer function The RSM 8R will display a screen which allows you to modify parameters for the selected Ping No Answer Reboot Profile Note that this screen functions identically to the...

Страница 85: ...1 Adding Scheduled Reboots The RSM 8R allows up to 54 Scheduled Reboots to be defined The Add Scheduled Reboot menu allows you to define the following parameters for each new Scheduled Reboot Schedul...

Страница 86: ...using a password that allows Administrator level commands and then use the Scheduled Reboot menu s View Modify Scheduled Reboot function The RSM 8R will display a screen which lists all defined param...

Страница 87: ...s and parameters must first be defined as described in Section 5 9 11 Email alarm notification will then be sent for all alarms that are enabled as described in this Section In order to send alarm not...

Страница 88: ...erature drops to an acceptable level Notes In order for the RSM 8R to provide alarm notification via Email communication parameters must first be defined as described in Section 5 9 11 In order for th...

Страница 89: ...ation for this alarm Default On Note The Email Message parameter offers four different options On Off On Copy to All Triggers or Off Copy to All Triggers If either of the Copy to All Triggers options...

Страница 90: ...the user specified plugs whenever the temperature exceeds the Alarm Set Threshold value Default Disable Plug State Determines whether the selected plugs plug groups will be switched On or Off when Loa...

Страница 91: ...ff whenever the temperature exceeds the Alarm Set Threshold Default undefined Notes In the Text Interface Plug Group Access is configured by typing 5 pressing Enter and then selecting the desired Plug...

Страница 92: ...M 8R will wait to resend an email message generated by this alarm when the initial attempt to send the notification was unsuccessful Default 60 Minutes Notify Upon Clear When this item is enabled the...

Страница 93: ...the RSM 8R command mode using a password that permits Administrator Level commands Enable the Heartbeat function and select the Any to Any port mode at the desired Serial Port as described in Section...

Страница 94: ...Copy to All Triggers or Off Copy to All Triggers If either of the Copy to All Triggers options is selected then email notification for all other alarms will be switched On or Off as indicated by this...

Страница 95: ...ification communication parameters must first be defined as described in Section 5 9 11 In order for the RSM 8R to provide Syslog Message notification Syslog parameters must first be defined and Syslo...

Страница 96: ...mail notification for all other alarms will be switched On or Off as indicated by this parameter For example If Off Copy to All Triggers is selected then Email notification will be disabled for all ot...

Страница 97: ...Invalid Access Lockout parameters as described in Section 5 3 2 set the Lockout Attempts and Lockout Duration as you would normally and then set the Lockout Enable parameter to Off In order for the R...

Страница 98: ...Lockout Notify Upon Clear When this item is enabled the RSM 8R will send additional notification when the situation that caused the alarm has been corrected For example when Notify Upon Clear is enabl...

Страница 99: ...command mode using a password that permits Administrator Level commands The Power Cycle Alarm configuration menu offers the following parameters Trigger Enable Enables Disables the trigger for this al...

Страница 100: ...d Alarm is not enabled the RSM 8R can still send SNMP Traps to notify you when the amount of accumulated data at a buffer mode port exceeds the Buffer Threshold value providing that SNMP Trap Paramete...

Страница 101: ...er alarms too Address 1 2 and 3 These parameters are used to select which of the three email addresses defined via the Email Messages menu see Section 5 9 11 will receive the email alarm notification...

Страница 102: ...sage Syslog parameters must first be defined and Syslog Messages must be enabled as described in Section 5 9 2 and Section 11 In order for the RSM 8R to provide alarm notification via SNMP Trap SNMP p...

Страница 103: ...is alarm Default On Address 1 2 and 3 These parameters are used to select which of the three email addresses defined via the Email Messages menu see Section 5 9 11 will receive the email alarm notific...

Страница 104: ...ord that permits Administrator Level commands The Lost Voltage Alarm Configuration menu offers the following parameters Trigger Enable Enables Disables the trigger for this alarm When Disabled this al...

Страница 105: ...Address parameters can be used to select one or any combination of the addresses defined via the Email Messages menu Default All On Note If Email addresses have been previously specified then the text...

Страница 106: ...ng items Product The make model number of the RSM 8R unit Serial Number Displays the serial number for the RSM 8R unit providing that the serial number has been previously defined via the Systems Para...

Страница 107: ...Status screen and Plug Status screen show the current status of the RSM 8R s serial ports and switched plugs The Port Status screen lists the user defined port name and port mode for each serial port...

Страница 108: ...ned name for each serial port Username When a user is connected to a given serial port this column will show the name of the user account that initiated the connection Status The connection status of...

Страница 109: ...m Name The user defined name for each switched outlet Status The current On Off status of each switched outlet If the Status column includes an asterisk this means that this outlet is busy completing...

Страница 110: ...d side of the screen The RSM 8R will display a screen that lists all currently defined Plug Groups Click the check box es next to the Plug Group s that you want to review and then click on the Get Plu...

Страница 111: ...logged event occurred Time The time that the logged event occurred Username The name of the user account that initiated the logged event Description A brief description of the nature of the logged ev...

Страница 112: ...t permits Administrator or SuperUser level commands and then proceed as follows Text Interface Type L and press Enter The Display Logs menu will be shown At the Display Logs menu key in the number for...

Страница 113: ...e internal Modem Port is named Modem by default Status The connect status for each port When the port is connected this column will list the number of the other port connected to this port If the colu...

Страница 114: ...hat account and will not display parameters for the Network Port The W command uses the following format W xx Enter Where xx is the desired port number If the W command is invoked at a serial port by...

Страница 115: ...select the desired switching option from the dropdown menu and click on the Confirm Plug Actions button When the Confirm Plug Actions button is pressed the RSM 8R will display a screen which lists the...

Страница 116: ...e selected action s and asks for confirmation before proceeding To implement the selected plug group action s click on the Execute Plug Group Actions button The RSM 8R will display a screen which indi...

Страница 117: ...ady being switched or rebooted by a previous command then the new command will be placed in a queue until the plug is ready to receive additional commands If an asterisk appears in the Status column f...

Страница 118: ...r or name of the desired plug or Plug Group Note that the BOOT command can also be entered as BO For example BOOT 3 Enter or BO ATMSWTCH Enter 4 Set All Plugs to Power Up Defaults Type DPL and press E...

Страница 119: ...ff enter either of the following commands OFF 1 3 4 Enter or OFF 1 3 4 Enter Note When the or are used do not enter spaces between the plug name or number and the plus sign or comma 2 Switch a Series...

Страница 120: ...also the default mode for Port 1 9 3 1 1 Connecting Ports Two different types of connections can be made between RSM 8R serial ports Resident Connections and Third Party Connections The RSM 8R allows...

Страница 121: ...R serial ports are not allowed to initiate a Resident Connection to the Network Port Third Party Connections Serial ports are not allowed to connect another port to the network port For example Port 1...

Страница 122: ...o enter a carriage return before or after the logoff character b Three Characters Uses the Enter LLL Enter format where L is the logoff character For example if the logoff character is then the discon...

Страница 123: ...exit command mode after disconnecting The Timeout value also applies to unconnected ports that are left in command mode When an unconnected port is left in command mode and no additional activity is d...

Страница 124: ...t available Modem type C MODEM Enter Hunt Group Example 2 1 Ports 3 4 and 5 are Any to Any Mode ports All three ports are named SERVER 2 Your resident port is Port 1 If you want to connect Port 2 to t...

Страница 125: ...Modem Mode Port then issue the R command using the following format R xx Enter Where xx is the number of the port buffer to be read Notes The R command is not available to ViewOnly level accounts In...

Страница 126: ...s the amount of Buffer Memory currently used by each port The RSM 8R uses buffer memory in two different ways depending on the user selected port mode Any to Any Passive and Modem Mode Ports When two...

Страница 127: ...nternal Modem Port cannot be changed When an external modem is installed at an RSM 8R port other ports can use the modem for calling out To call out invoke the C command to connect to the port then ac...

Страница 128: ...that when the K Send SSH Key command is invoked the RSM 8R can also provide you with a public SSH key which can be used to streamline connection to the RSM 8R when using SSH protocol Although you can...

Страница 129: ...w Direct Connections using either Standard Telnet or Raw Socket Mode note that the Direct Connect option Port Configuration Menu Item 31 may be set to either On Password or On No Password 10 3 2 Confi...

Страница 130: ...nect password enabled proceed as follows i Access the Serial Port configuration menu for the desired RSM 8R serial port and then use the Direct Connect option to select the On Password option After On...

Страница 131: ...to create a Raw Socket Direct Connection the Raw Socket Access parameter for the Network Port must be enabled as described in Section 5 9 2 When establishing a Direct Connection the correct TCP port n...

Страница 132: ...nd which is defined via the Port Configuration menus cannot be used to terminate a Direct Connection Any RSM 8R port that allows Administrator or SuperUser level commands can terminate a direct connec...

Страница 133: ...d Telnet connection access the Text Interface via a free Serial Port using an account that permits Telnet Access and Outbound Access and then invoke the TELNET command using the following format TELNE...

Страница 134: ...d will not function To create an outbound SSH connection access the Text Interface via a free Serial Port using an account that permits SSH Access and Outbound Access and then invoke the SSH command u...

Страница 135: ...Clock and Calendar and or configure and enable the NTP server feature 3 Network Parameters Menu Access the Network Parameters Menu as described in Section 5 9 then set the following parameters a Sysl...

Страница 136: ...ommands 2 Serial Port Parameters If you wish to generate SNMP Traps that will notify you when a Buffer Mode Port buffer reaches the user defined Buffer Threshold access the Serial Port Parameters menu...

Страница 137: ...To enable the SNMP Trap feature you must define at least one SNMP Manager SNMP Traps are automatically enabled when at least one SNMP Manager has been defined The SNMP Trap submenu in the Text Interf...

Страница 138: ...can be found on the WTI web site http www wti com The WTI RSM TSM MIB txt document can be compiled for use with your SNMP client 13 2 SNMPv3 Authentication and Encryption The major limitations of SNMP...

Страница 139: ...the account does not have access to the port and a 1 indicates that the user does have access to the port Note The number of ports specified in the userPortAccess string must not exceed the number of...

Страница 140: ...parameters will be set to defaults if not specified To create the user issue a SET request on the userSubmit object 13 3 3 Modifying Users For the index corresponding to the user you wish to modify i...

Страница 141: ...to For the last plug you wish to set before executing the commands use values 5 8 instead which will invoke the requested commands all at once 13 4 2 Controlling Plug Groups ON OFF BOOT and DEFAULT c...

Страница 142: ...this port portTable portStatus Shows the connection status of each port If a port is connected the portStatus object will return the number of the other port in the connection pair free Disconnect por...

Страница 143: ...s a Set Trap which indicates that the alarm has been triggered and a Clear Trap which indicates that the alarm has been cleared overTemperatureInitialSetTrap Indicates that the Over Temperature Initia...

Страница 144: ...merely a warning that the RSM 8R is not recognized and that you may not be connecting to the site that you intended Signed certificates must be created via an outside security service e g VeriSign Th...

Страница 145: ...n Name A domain name that will be used to identify the RSM 8R unit If you will use a Self Signed certificate then this name can be any name that you choose and there is no need to set up your domain n...

Страница 146: ...ates that the Self Signed certificate has been successfully created and saved b Click on the Yes button to proceed The RSM 8R will prompt you to enter a user name and password After keying in your pas...

Страница 147: ...nterface using an HTTPS connection For example if the common name has been defined as service wti com then you would enter https service wti com in your web browser s address field If the Signed Certi...

Страница 148: ...our terminal emulation program and access the Text Interface command mode using an account that permits Administrator level commands 2 When the command prompt appears type U and press Enter The RSM 8R...

Страница 149: ...name and directory path 4 Your terminal emulation program will send the ASCII text file to the RSM 8R When the terminal program is finished with the upload make certain to terminate the Upload mode N...

Страница 150: ...l Reboot options Option 4 is used to restore the configuration backup file The date shown next to option 4 indicates the date that you last changed and saved unit parameters If the daily automatic con...

Страница 151: ...upport Firmware Upgrade_Utility Please refer to the documentation included in the zip file for further instructions 16 2 The Upgrade Firmware Function Alternate Method The Upgrade Firmware function pr...

Страница 152: ...is selected the RSM 8R will start the receiving servers and wait for an FTP SFTP client to make a connection and upload a valid firmware binary image 4 To proceed with the upgrade select either optio...

Страница 153: ...nd Save Parameters you may then reestablish a connection with the RSM 8R using your former IP address If you initially selected Start FTP SFTP Servers and Default Parameters you must then login using...

Страница 154: ...asterisk this means that the plug is currently busy and is in the process of completing a previously issued command If a new command is issued to a busy plug then the new command will placed into a q...

Страница 155: ...uration TEST Enter X In Administrator and SuperUser modes all ports and plugs are displayed In User and ViewOnly modes the status screen will only include the ports and plugs allowed by the account Us...

Страница 156: ...er level or View Only level account the resulting screen will only display parameters for the ports allowed by the account For more information please refer to Section 8 6 Availability Administrator S...

Страница 157: ...o the RSM 8R s Network Port For more information please refer to Section 8 2 Availability Administrator SuperUser User ViewOnly Format SN Enter H Help Displays a Help Screen which lists all available...

Страница 158: ...nd Availability Administrator SuperUser User ViewOnly Format X Enter C Connect Establishes a bidirectional connection between two ports For more information see Section 9 3 There are two types of conn...

Страница 159: ...orts enter an asterisk To disconnect a Telnet session enter the Nn format Network Port Number Example To disconnect Port 2 from Port 3 without the Sure prompt access the Command Mode from a third port...

Страница 160: ...also be entered as BO Note When this command is invoked in Administrator Mode or SuperUser Mode it can be applied to all RSM 8R plugs and Plug Groups When this command is invoked in User Mode it can o...

Страница 161: ...account Availability Administrator SuperUser User Format ON n Y Enter Where n The number or name of the plug s or Plug Group s that you intend to Switch On To apply the command to several plugs enter...

Страница 162: ...all plugs allowed by your account enter an asterisk character Y Optional Suppresses the command confirmation prompt Examples Assume that your account allows access to Plug 2 and Plug 3 To switch Plugs...

Страница 163: ...order to prevent further access attempts When the UL command is invoked the RSM 8R will immediately unlock all ports and protocols that are currently in the locked state Availability Administrator For...

Страница 164: ...Serial Ports Broadcasts text or commands to a user specified selection of RSM 8R Serial Ports Notes The Broadcast command will only be applied to Serial Ports that are configured for Any to Any Mode...

Страница 165: ...erial port PL Set Plug Parameters Displays a menu that is used to select options and parameters for the RSM 8R s switched outlets plugs All functions provided by the PL command are also available via...

Страница 166: ...r to Section 7 2 Availability Administrator Format RB Enter AC Alarm Configuration Parameters Displays a menu that is used to configure and enable the RSM 8R s monitoring and alarm functions For more...

Страница 167: ...ed to copy parameters to RS232 ports For more information please refer to Section 5 8 3 Note To proceed with the Copy function after selecting new parameters press Esc the RSM 8R will then display the...

Страница 168: ...t for Modem Mode the DTR output at either port reflects the DCD input at the other end b If neither port is set for Modem Mode DTR output is held high active 2 When not connected a If the port is set...

Страница 169: ...that the pins in the connectors at each end of the cable are linked to each other In Straight Cables the pins on each connector are linked to the same pin number on the connector at the other end of t...

Страница 170: ...nsole Port When connecting a DB 9M DTE device to an RJ 45 Serial Port on the RSM 8R please refer to Figure B 3 and Figure B 4 below RJ 45 DB 9F Pin No Pin No Signal 1 2 3 4 5 X 6 7 8 8 1 2 5 3 4 7 CTS...

Страница 171: ...rial Port on the RSM 8R please refer to Figure B 5 and Figure B 6 below RJ 45 DB 25M Pin No Pin No Signal 1 2 3 4 5 X 6 7 8 5 8 3 7 2 20 4 CTS DCD TXD RXD GND DTR RTS Pin 8 Pin 1 Pin 1 Male Figure B 5...

Страница 172: ...a DB 35F DCE device to an RJ 45 serial port on the RSM 8R please refer to Figure B 7 and Figure B 8 below RJ 45 DB 25M Pin No Pin No Signal 1 2 3 4 5 X 6 7 8 4 20 2 7 3 8 5 RTS DTR RXD TXD GND DCD CTS...

Страница 173: ...serial port on an RSM 8R unit please refer to Figure B 9 below RSM 8R RJ 45 DCE Serial Port Rollover RJ 45 Cable RJ 45 DCE Serial Port Cisco Router Sun Router or other Device with RJ 45 DCE Interface...

Страница 174: ...ront Panel Facing Upwards Use the screws provided with the mounting kit to secure the wall mount brackets to the RSM 8R4 DCM unit as shown in Figure C 1 Use six screws per mounting bracket as shown Fr...

Страница 175: ...n equipment rack first use four screws to secure the Rack Mount Brackets to the sides of the unit as shown in Figure C 2 then secure the Rack Mount brackets to your equipment rack as shown in Figure C...

Страница 176: ...ch the DIN Mounting Brackets to the RSM 8R4 DCM unit as shown in Figure C 4 and then attach the DIN Mounting Brackets to your DIN Rail Note Make certain that the spring loaded latches on the DIN Mount...

Страница 177: ...TS Both or None Data Rate 300 to 115 2K bps all standard rates Internal Modem V 34 Physical Environmental Dimensions RSM 8R4 1 and RSM 8R4 2 Width 19 48 3 cm Including Rack Brackets Depth 6 5 16 5 cm...

Страница 178: ...e of the unit its serial number and a description of its symptoms If the unit should need to be returned for factory repair it must be accompanied by a Return Authorization number from Customer Servic...

Страница 179: ...lematic Inc Copyright Western Telematic Inc 2011 September 2011 Part Number 13851 Revision J Trademarks and Copyrights Used in this Manual Hyperterminal is a registered trademark of the Microsoft Corp...

Отзывы: