Original Operating Instructions
BATI0XXX-ES-1-ZZZ-1
Commissioning
O_BATI_0XXX-ES-1-ZZZ-1_V1.4_GB
Seite
42
von
60
5.2
Starting the Product
WARNING!
Risk of injury due to high voltage when measuring!
Danger to life due to high voltage.
•
Take measurements only with appropriate measurement devices.
•
During measurement, the AC circuit breaker must be turned off
and all fuse inserts must be removed.
•
The product shall be started only by authorized and trained
electricians.
Procedure:
1.
Measure
the DC voltage from plus to minus connection on the DC switch
disconnector (Section 0)
NOTICE: The voltage must be positive, and the measured values must be within the
allowed tolerance range (Section 11.2.1).
2.
Measure
the AC voltage on the terminals of the AC circuit breaker (Section
Phase to Phase
Phase to PE
NOTICE: The measured values must be within the allowed tolerance range (Section
11.2.1).
3.
Check
rotary field of AC voltage.
4.
Switch
AC circuit breaker (
–Q2) to
ON
position.
NOTICE:
The DC switch disconnector is operated automatically.
5.
Close
all doors.
6.
Unlock
the Enable switch.
NOTICE: Operation is started after the appropriate checks via the software interface.