3.4.7 Customer Feedback Insulation Monitoring Device (Optional)
The product offers the possibility to evaluate the feedback contact of the insulation
monitoring device by the customer. The connection is provided as potential-free
contact at the terminal strip (-X2).
Mode of operation of the insulation monitoring device:
If the measured value drops below the set threshold value, the output relays switch into
the fault state. If the measured value exceeds the threshold value plus hysteresis, the
output relays switch back into their original state.
Table 3: Operating mode of insulation monitoring device
Relay state
Terminal
Contact
Original state
(-X2.6) to (-X2.8)
close
(-X2.6) to (-X2.7)
open
Fault state
(-X2.6) to (-X2.8)
open
(-X2.6) to (-X2.7)
close
3.4.8 Customer Feedback Product (Optional)
The operating status of the control card feedback contacts can be queried via terminal
(
–X2) located in the control cabinet.
Operating status
Terminal
Contact
Ready for operation
(-X2.1) to (-X2.2)
open
(-X2.1) to (-X2.3)
close
Not
Ready for operation
(-X2.1) to (-X2.2)
close
(-X2.1) to (-X2.3)
open
3.4.9 Temperature Sensor Connection
The ambient temperature can be visualized via the user interface.
Requirement (not included in scope of delivery):
•
Temperature sensor e.g. PT100
Procedure:
1.
Find
terminal strip (
–X15) (Figure 6).
2.
Connect
the temperature sensor to terminals (
–X15.1) to (–X15.2).