TD_PCM1x_Packages_Installation_09.04_GB
33
7 Accuracy
Measuring values
Display and ranges
Accuracy
Notes
Frequency
Generator f
L1N
, f
L2N
, f
L3N
15.0-85.0 Hz
1 %
-
Busbar f
L12
15.0-85.0 Hz
1 %
-
Mains f
L1N
, f
L2N
, f
L3N
40.0-85.0 Hz
1 %
-
Voltage
Generator V
L1N
, V
L2N
, V
L3N
0-400 V
1 %
Transformer ratio adjustable
V
L12
, V
L23
, V
L31
0-400 V
1 %
Busbar V
L12
0-400 V
1 %
Transformer ratio adjustable
Mains V
L1N
, V
L2N
, V
L3N
0-400 V
1 %
Transformer ratio adjustable
V
L12
, V
L23
, V
L31
0-400 V
1 %
Current
Generator I
L1
, I
L2
, I
L3
0-9,999
A
1
%
-
Max. value
I
L1
, I
L2
, I
L3
0-9,999 A
1 %
Slave pointer
Mains I
L1
0-9,999
A
1
%
-
Real power
Current total real power value
-
32.0-0-
+
32.0 MW
2 %
-
Reactive power
Current value in L1, L2, L3
-
32.0-0-
+
32.0 Mvar
2 %
-
cos
Current value cos L1 i0.00-1.00-k0.00
2
%
-
Miscellaneous
Real energy
0-4,200 GWh
2 %
not calibrated
Operating hours
0-65,000 h
-
Maintenance call
0-9,999 h
-
Start counter
0-32,750
-
Battery voltage
10-30 V
1 %
-
Pickup speed
f
N
± 40 %
-
Analog inputs (Packages P01)
0/4-20 mA
freely scaleable
-
Pt100 0-250
°C
not
calibrated
0-180 Ohm
freely scaleable
for VDO sensors
0-360 Ohm
freely scaleable
for VDO sensors
Reference conditions (to measure the accuracy):
•
Input voltage............................ sinusoidal rated voltage
•
Input current............................. sinusoidal rated current
•
Frequency ............................... rated frequency ± 2 %
•
Power supply ........................... rated voltage ± 2 %
•
Power
factor
cos .................... 1.00
•
Ambient
temperature ................. 23
°C ± 2 K
•
Warm-up period....................... 20 minutes