24
TD_PCM1x_Packages_Installation_09.04_GB
5.6 Relay
Outputs
5.6.1 Controller
Outputs
Enable GCB
max. 250 V AC
Command: close GCB
Command: close MCB
Command: open MCB
GCB
MCB
MCB
GCB
41
42
14
17
40
39
16
15
Figure 5-14: Relay outputs – Controller outputs – CB activation
Make
cont.
Description A
max
14/15
Command: close GCB
2.5 mm²
16/17
[PCM1-M]
Command: close MCB
2.5 mm²
39/40
[PCM1-M]
Command: open MCB
2.5 mm²
41/42
Command: open GCB
2.5 mm²
Table 5-15: Relay outputs - terminal assignment
5.6.2 Relay
Manager
A
B
Relay output
external device
max. 250 V AC
Figure 5-15: Relay outputs – Relay manager
Make
cont.
Description A
max
18/19
Readiness for operation
2.5 mm²
43/44
Operating magnet/Stopping magnet
2.5 mm²
45/46 Starter
2.5
mm²
74/75
Relay [R1] (Relay manager)
2.5 mm²
76/77
Relay [R2] (Relay manager)
2.5 mm²
78/79
Relay [R3] (Relay manager)
2.5 mm²
80/81
Relay [R4] (Relay manager)
2.5 mm²
82/83
Relay [R5] (Relay manager)
2.5 mm²
37/38
Relay [R6] (Relay manager; pre-assigned: Preheat/Ignition ON)
2.5 mm²
47/48
Relay [R7] (Relay manager; pre-assigned: Centralized alarm horn)
2.5 mm²
Table 5-16: Relay manager - terminal assignment