22
TD_PCM1x_Packages_Installation_09.04_GB
5.4
Analog Inputs (Packages P01)
GND
C
C
A
B
C
A
a
I
B
A
B
Analog input
VDO 0..180/380 Ohm
Analog input
0/4..20 mA
Analog input
Pt100
Figure 5-11: Analog inputs - Package P01
Terminal A
max
A
B
C
Description
(according to DIN 40 719 Part 3, 5.8.3)
93
94
95
Analog input 1 [T1]
0/4-20 mA
, configurable function:
- Alarm input or
- Set value input or
- Actual value input
1.5 mm²
96
97
98
Analog input 2 [T2]
0/4-20 mA
, configurable function:
- Alarm input or
- Set value input or
- Actual value input
1.5 mm²
99
100
101
Analog input 3 [T3]
0/4-20 mA
, configurable function:
- Alarm input or
- Set value input or
- Actual value input
1.5 mm²
102
103
104
Analog input 4 [T4]
Pt100
, configurable function:
- Alarm input or
- Actual value input
1.5 mm²
105
106
107
Analog input 5 [T5]
Pt100
, configurable function:
- Alarm input or
- Actual value input
1.5 mm²
108
109
110
Analog input 6 [T6]
VDO pressure 0-5/10 bar or 0-72.5/145 psi 0-
180 Ohm
, configurable function:
- Alarm input or
- Actual value input
1.5 mm²
111
112
113
Analog input 7 [T7]
VDO temperature 30-120°C or 86-248°F 0-380
Ohm
, configurable function:
- Alarm input or
- Actual value input
1.5 mm²
Table 5-12: Analog inputs - terminal assignment