TD_PCM1x_Packages_Installation_09.04_GB
21
5.3.3
Operation Mode Selection Via DI (Package P01, from V4.3010)
This package enables to select the operation mode using the terminals 127 and 128 externally from
4.3010. The discrete inputs can be connected using positive or negative logic as described above.
Terminal Associated
common
Description
(according to DIN 40 719 Part 3, 5.8.3)
A
max
127
Control input [terminal 127]
- Operation mode
STOP
2,5 mm²
128
124
Control input [terminal 128]
- Operation mode
AUTOMATIC
2,5 mm²
Table 5-11: Discrete inputs - operation mode selection
NOTE
The selection of the operation mode is only possible if the discrete input on terminal 63 (Operation mode selector
blocked) is energized. More detailed information can be found in the configuration manual (37276A) under 'Block
operation mode selector switch via terminal 63'.