32
TD_PCM1x_Packages_Installation_09.04_GB
Interface
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Service interface
-
Version.............................................................................................................. RS232
-
Signal level.............................................................................................................5 V
Level conversion and insulation by using FL-CABLE-RS232
CAN bus interface
isolated
-
Insulation voltage .......................................................................................... 1,500 Vdc
-
Version...........................................................................................................CAN bus
-
Internal line termination................................................................................ Not available
Battery (Packages P01) -----------------------------------------------------------------------------------------------------------------------------------------------------------------
-
Type...................................................................................................................NiCd
-
Durability (at operation without power supply)...............................................approx. 5 years
-
Battery field replacement ................................................................................not possible
Housing -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-
Type.......................................................................................APRANORM DIN 43 700
-
Dimensions (W × H × D)................................................................144 × 144 × 118 mm
-
Front cutout (W × H)............................................................138 [+1.0] × 138 [+1.0] mm
-
Wiring............................................................ screw-plug-terminals 1.5 mm² oder 2.5 mm²
-
Recommended locked torque .............................................................................. 0.5 Nm
use 60/75 °C copper wire only
use class 1 wire only or equivalent
-
Weight ............................................................................................... approx. 1,000 g
Protection ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-
Protection system..........................................................IP42 from front for proper installation
IP54 from front with gasket
IP21 from back
-
Front folio .............................................................................................insulating surface
-
EMC test (CE) .................................................tested according to applicable EN guidelines
-
Listings ............................................................. CE marking; UL listing for ordinary locations
-
Type approval.................................................................UL/cUL listed, Ordinary Locations