![Woodward 2301E-ST Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/woodward/2301e-st/2301e-st_installation-and-operation-manual_995875073.webp)
Manual 26694
2301E-ST
Woodward
71
Table 3-2. Communication Error Code
CODE NAME
MEANING
00
NO ERROR
Error free
The following are returned to the master.
01 ILLEGAL
FUNCTION
Message function received is not an allowable action for addressed slave.
(Unsupported or illegal function code).
02 ILLEGAL
DATA
ADDRESS
Address referenced in data field is not an allowable address for the
addressed slave location. (Master requested data, which is not configured
from slave).
03 ILLEGAL
DATA
VALUE
Amount of data requested from slave was too large for slave to return in a
single response. Woodward maximum is 118 registers
The following are displayed only.
09 CHECKSUM
ERROR
Error in the checksum. Can indicate link quality and/or noise problems.
10 GARBLED
MESSAGE
Data received by the slave, but it is too short to be a valid Modbus
message/command.
02 BAUD RATE
dflt=12 (8, 12)
Set the Baud rate, which defines the transfer rate for port communications.
8=9600 9=19200
10=38400 11=57600
12=115200
03 BAUD RATE IS SET FOR
Shows the selected Baud rate.
04 DATA BITS
dflt=2 (1, 2)
Set the Data bits input defines the protocol for the number of data bits in the data packets.
1=7
2=8
05 DATA BITS ARE SET FOR
Shows the selected data bits.
06 STOP BITS
dflt=1 (1, 3)
Set the Stop bits, which defines the number of stop bits for the communications protocol. Stop bits specify
the time that elapses between transmitted characters.
1=1 stop bit
2=2 stop bits
3=1.5 stop bits
07 STOP BITS ARE SET FOR
Shows the selected stop bits setting.
08 PARITY
dflt=1 (1, 3)
Set the Parity input defines protocol for the parity. If you selected 8 data bits select '1' for none.
1=OFF (none)
2=ODD
3=EVEN
09 PARITY IS SET FOR
Shows the parity setting.
10 DRIVER IS SET FOR
RS 232
15 TIME OUT (SEC)
dflt=4.0
(0.0,
100.0)
Set the Time-out Number of Seconds input defines the Modbus link dead time allowed before a link error
occurs.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...