![Woodward 2301E-ST Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/woodward/2301e-st/2301e-st_installation-and-operation-manual_995875044.webp)
Manual 26694
2301E-ST
Woodward
42
CONFIGURE: D**ANALOG INPUT OPTIONS**
Figure 3-6. Configure: D**ANALOG INPUT OPTIONS** Menu
01 CONFIGURATION ERROR?
dflt=FALSE (FALSE, TRUE)
Displays a TRUE if any of the two analog inputs are set the same. Not Used and Monitor Signal Input can
be set the same. Displays a FALSE if the analog input configuration is correct.
02 SEL AI #1 FUNCTION (1-6)
dflt=1 (1, 6)
Select one of the following parameters for Analog Input #1 at terminal 19-21.
1=INPUT #1 NOT USED
2=REMOTE SPEED SETPOINT
3=MONITOR SIGNAL INPUT
4=SYNCHRONIZER BIAS SIGNAL
5=REMOTE PROCESS SETPOINT
6=PROCESS SIGNAL
03 DISPLAY AI #1 FUNCTION
Displays the function selected for Analog Input #1.
04 SEL AI #1 TYPE (1-4)
dflt=1 (1, 4)
This value is used to set the Analog Input #1 type.
1 = 4 – 20 (mA)
2 = 0 – 5 (V)
3= ± 2.5 (V)
4= 1 – 5 (V)
05 DISPLAY AI #1 TYPE
Displays configured Analog Input #1 type.
06 USE INPUT #1 FAIL TRIP
dflt=FALSE (FALSE, TRUE)
Set to TRUE to use the trip function that Analog Input #1 has failed.
Input Set For:
Low Trip Point:
High Trip Point:
4–20 mA
2.0 mA
22.0 mA
0–5 Vdc
–0.63 Vdc
5.63 Vdc
±2.5 Vdc
–3.13 Vdc
+3.13 Vdc
1–5 Vdc
0.5 Vdc
5.5 Vdc
07 SEL AI #2 FUNCTION (1-6)
dflt=1 (1, 6)
Select one of the following parameters for Analog Input #2 at terminal 22-23.
1=NOT USED
2=REMOTE SPEED SETPOINT
3=MONITOR SIGNAL INPUT
4=SYNCHRONIZER BIAS SIGNAL
5=REMOTE PROCESS SETPOINT
6=PROCESS SIGNAL
08 DISPLAY AI #2 FUNCTION
Displays the function selected for Analog Input #2.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...