06 ANALOG INPUT #1 FAIL (4)
displays the status of Analog Input #1 (if configured). A failed input is detected
when the analog #1 exceeds the following ranges:
Input Set For:
Low Trip Point
High Trip Point
4–20 mA
2.0 mA
22.0 mA
0–5 Vdc
–0.63 Vdc
5.63 Vdc
±2.5 Vdc
–3.13 Vdc
+3.13 Vdc
1–5 Vdc
0.5 Vdc
5.5 Vdc
07 ANALOG INPUT #2 FAIL (5)
displays the status of Analog Input #2 (if configured). A failed input is detected
when the analog #2 exceeds the following ranges:
Input Set For:
<Low Trip Point
>High Trip Point
4–20 mA
2.0 mA
22.0 mA
0–5 Vdc
–0.63 Vdc
5.63 Vdc
±2.5 Vdc
–3.13 Vdc
+3.13 Vdc
1–5 Vdc
0.5 Vdc
5.5 Vdc
08 MODBUS ISSUED TRIP (6)
displays the status of the Modbus Issued Trip (if configured). A trip is
detected when an input from the Modbus controller has issued a trip command.
09 TEST MODE (7)
displays the status of Test Mode input. A trip is detected when the Actuator
Calibration or the Enable Hardware Test is enabled.
10 EXTERNAL SHUTDOWN (8)
displays the status of SHUTDOWN / RUN DISCRETE input. A shutdown is
detected when the discrete input on terminal 34 is FALSE.
11 STUCK IN CRITICAL (9)
displays the status of a shutdown caused by a stuck in critical band failure.
12 SHUTDOWN ACKNOWLEDGE
dflt=FALSE (FALSE, TRUE)
When set to TRUE will reset the SHUTDOWN RELAY discrete output. (See also description of RESET CLEARS TRIPS
in the configure menu C**DISCRETE OUT OPTIONS**.
D** ALARMS **
Figure 3-12. Service: D** ALARM ** Menu
This menu displays the status of the alarm modes.
01 ALARM STATUS
gives the existing alarm conditions. If control has alarms, it displays TRUE. If no
alarms exist, it displays FALSE.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...