![Woodward 2301E-ST Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/woodward/2301e-st/2301e-st_installation-and-operation-manual_995875070.webp)
Manual 26694
2301E-ST
Woodward
68
16 RELAY 4 SELECTED AS
displays the function selected for terminal 47. This relay is selected in the
configure menu - C**DISCRETE OUT OPTIONS**
17 RELAY 4 LEVEL SW (1-7)
dflt=1 (1, 7)
Select one of the following parameters for discrete output at terminals 47 when it was selected as a level
switch.
1=NOT USED
2=ACTUAL SPEED
3=SPEED SETPOINT
4=VALVE LIMITER SETPOINT
5=ACTUATOR DEMAND
6=GENERATOR OUTPUT (LOAD SENSOR)
7=MONITOR SIGNAL
18 RELAY 4 LEVEL SELECT FOR
displays the level function selected for terminal 47.
19 RELAY 4 ON LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch ON setting in engineering units. There is an ON and an OFF setting for each level
switch option. This allows the user to program the desired hysteresis for the function selected.
20 RELAY 4 OFF LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’).
The Discrete outputs can be changed for other functions when the
turbine is running. Therefore, do not change the Configured
Shutdown Relay when the turbine is running.
R** DISPLAY D_I/O STATUS **
Figure 3-29. Service: R** DISPLAY D_I/O STATUS ** Menu
This section has no adjustments to set, it is used only for display status of discrete inputs and the status
of the discrete outputs.
01 DI EXTERNAL SHUTDOWN
indicates status of discrete input A.
02 DI RESET
indicates status of discrete input B.
03 DI START / UNLOAD
indicates status of discrete input C.
04 DI RAISE SPEED
indicates status of discrete input D.
05 DI LOWER SPEED
indicates status of discrete input E.
06 DISCRETE INPUT F
indicates status of discrete input F.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...