Manual 26694
2301E-ST
Woodward
60
THIS MENU IS USED TO SETUP THE SYNCHRONIZER LOGIC.
01 ENBL SYNC INPUT
displays whether the sync input is being used. If it is TRUE, the SYNC INPUT
can be used. This should be activated in menu: Configure D** ANALOG INPUT OPTIONS
02 SYNC INPUT SCALE (%/V)
dflt=0.7
(0.1,
5.0)
Should be set to the Analog Input sync input scale.
03 SYNC BIAS SPD (RPM)
displays the value of sync bias speed.
04 TURBINE SPEED (RPM)
displays actual turbine rpm.
05 SPD REF (RPM)
displays turbine speed setpoint rpm.
L* VALVE LIMITER SET **
Figure 3-23. Service: L* VALVE LIMITER SET ** Menu
THIS MENU IS USED TO SET UP THE VALVE LIMITER CONTROL.
01 ENABLE MANUAL CNTRL RAMP
dflt=FALSE
(FALSE,TRUE)
Set this value to TRUE to manually control the valve ramp. MANUAL CNTRL RAMP SETPNT is used
manually lower the ramp. This value is low signal selected (LSS) with the turbine speed control. If
manually lowered below the speed control PID value, the valve ramp will take control.
02 MANUAL RAMP STATUS
displays the status of the MANUAL CONTROL RAMP.
03 MANUAL CNTRL RAMP SETPNT
dflt=100.0 (0.0, 100.0)
Set this value to manually control the valve ramp. This value is low signal selected (LSS) with the turbine
speed control.
If manually lowered below the speed control PID value, the valve
ramp will take control. This could cause serious consequences,
overspeed, or shutdown.
04 DISPLAY ACTUATOR %
displays the actual actuator output percentage.
05 ACTUAL VALVE RAMP %
displays the actual valve ramp output percentage.
06 MAN START RATE (%/SEC)
dflt=10.0 (0.0, 100.0)
If configured for MANUAL START, this value sets the valve ramp start rate in percent per second.
07 AUTO START RATE (%/SEC)
dflt=2 (0.0, 100.0)
If configured for a SEMI-AUTOMATIC START, this value sets the valve ramp start rate in percent per
second.
08 MAN/AUTO PID RAMP RATE
dflt=20.0 (1.0, 100.0)
If configured for a MANUAL START OR AUTOMATIC START MODE, this value sets the PID ramp that
sets the PID controller out of the way. This value is set in percent per second.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...