![Woodward 2301E-ST Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/woodward/2301e-st/2301e-st_installation-and-operation-manual_995875027.webp)
Manual 26694
2301E-ST
Woodward
25
Level Switch Options
1. TURBINE
SPEED
2. TURBINE SPEED REFERENCE
3. VALVE LIMITER REFERENCE
4. ACTUATOR
DEMAND
5. GENERATOR
OUTPUT
6. MONITOR
SIGNAL
Analog Output (Terminals 16-18)
Connect readout wiring to terminals 16(+), 17(–), and 18(shield) to use the control’s 4–20 mA Analog
Output. This Analog output is software configurable to function as one of the following readout options:
TURBINE
SPEED
TURBINE SPEED REFERENCE
VALVE LIMITER SETPOINT
ACTUATOR
DEMAND
GENERATOR
OUTPUT
SIGNAL
MONITOR
Verify that the output’s shielded wire has continuity its entire distance to the output device and is insulated
from all other conducting surfaces. This current driver based output is designed to drive into impedances
of up to 250
Ω
. This output is not isolated from the other control inputs and outputs, thus an isolation
device may be required with this output if the device being interfaced to is not isolated.
This analog output’s 4–20 mA current drive signal is directly proportional to the programmed function
signal that it is configured to represent. Refer to Chapter 3 for output configuration instructions. Its
clarifications are the same as Level Switches.
Communication Port
The control’s two serial communication ports are used to configure and service the unit. These ports are
on a common return and are isolated ports.
The RS-232 serial communication service port communicates using either the 2301E-ST Toolkit Service
Tool or the Control Assistant software. Refer to Figure 2-2 for plant wiring information.
The RS-422 serial communication port communicates using a Modbus RTU protocol, functioning as a
Modbus Slave device, via a RS-422 driver. The
2301E-ST can be fully operated and many values monitored via Modbus communications.
Alternatively Modbus communications can be used to interface with a PLC or plant DCS. Refer to Figure
2-2 for plant wiring information.
The communication port must be connected with an approved
jacketed serial communication cable. The connector must be
secured to the 2301E-ST to prevent contact with other circuits.
Released
Содержание 2301E-ST
Страница 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Страница 16: ...Manual 26694 2301E ST Woodward 14 Figure 2 1b 2301E ST Outline Drawing Hazardous Location Version Released...
Страница 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Страница 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Страница 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Страница 53: ...Manual 26694 2301E ST Woodward 51 Figure 3 14 Control Gain as a Function of Speed Error Released...
Страница 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...