MOTUS®C14 Operating Instructions
Page
69
of
73
94 762 000 B
Revision 03.2022
English.
21.4.5 Single-Phase Operation
– Configuration L2
ISDU-
Index
Name
Datatype
Length
(Bytes)
Description
Access
258
Nominal current
uint8
1
Unit in 100mA
Maximum value:
26: 2,6A device
66: 6,6A device
Read
Write
261
Trip class
uint8
1
0: 2E
1: 3
2: 5
3: 10A
4: 10
5: 20
6: 30
7: 40E
Read
Write
265
Undercurrent
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
269
Undercurrent
detection
–
Threshold
uint8
1
Unit in 100mA
Maximum value:
Actual set nominal
current
Read
Write
273
Undercurrent
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write
277
Undervoltage
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
281
Undervoltage
detection
–
Threshold
uint16
2
Unit in 10mV
Maximum value:
600V
Read
Write
285
Undervoltage
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write
289
Overvoltage
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
293
Overvoltage
detection
–
Threshold
uint16
2
Unit in 10mV
Maximum value:
600V
Read
Write
297
Overvoltage
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write