MOTUS®C14 Operating Instructions
Page
64
of
73
94 762 000 B
Revision 03.2022
0: Device OK
1: Short circuit
2: Overload
3: Load asymmetry
4: Phase loss
– Load
5: Undercurrent - Load
6: Supply loss
7: Undervoltage Supply
8: Overvoltage Supply
9: Overtemperature
10: Undervoltage Aux
11: Overvoltage Aux
12: Device error
13: Communication error
14: Missing device enable
(Phase specific, depending on Phase ID:
Subindex 4, Bit 7…6)
3
56
Nominal current [Einheit in 100mA]
(Phase specific when configured for 1~
operation, depending on Phase ID:
Subindex 4, Bit 7…6)
uint8
4
48
Bit 7…6:
Phase ID
0: Phase L1
1: Phase L2
2: Phase L3
Bit 4 - 5:
Reserved
Bit 3
…0:
Trip class
0: Class 2E
1: Class 3
2: Class 5
3: Class 10A
4: Class 10
5: Class 20
6: Class 30
7: Class 40E
(Phase specific when configured for 1~
operation, depending on Phase ID:
Subindex 4, Bit 7…6)
Enum
Enum
5
32
Load current [Unit in 10mA]
(Phase specific, depending on Phase ID:
Subindex 4, Bit 7…6)
uint16
6
16
Supply voltage [Unit in 10mV]
Corresponds to Chained Voltage:
Phase ID: L1; Chained Voltage L1L2
Phase ID: L2; Chained Voltage L2L3
Phase ID: L3; Chained Voltage L3L1
(Phase specific, depending on Phase ID:
Subindex 4, Bit 7…6)
uint16
7
8
Thermal load [Unit in %]
uint8