MOTUS®C14 Operating Instructions
Page
60
of
73
94 762 000 B
Revision 03.2022
Tripping curves (thermal equilibrium)
The tripping characteristics represent an overview of the times after which the MOTUS®C14
switches off due to an overload that has occurred. In the warm state, it is assumed that the
device previously ran in nominal operation for a longer period of time (>2h).
Figure 19
Tripping times (thermal equilibrium)
Table 2:
Tripping time [hh:mm:ss] (thermal equilibrium)
I / I
N
TC 2E
TC 3E
TC 5
TC 10A
TC 10
TC 20
TC 30
TC 40E
1,2
00:01:04 00:01:47 00:03:13 00:04:17 00:05:43 00:12:51 00:20:00 00:27:15
1,5
00:00:15 00:00:24 00:00:44 00:00:58 00:01:17 00:02:54 00:04:31 00:06:11
2
00:00:06 00:00:09 00:00:17 00:00:22 00:00:30 00:01:06 00:01:43 00:02:21
3
00:00:02 00:00:03 00:00:06 00:00:08 00:00:11 00:00:24 00:00:37 00:00:51
4
00:00:01 00:00:02 00:00:03 00:00:04 00:00:06 00:00:13 00:00:20 00:00:27
5
00:00:01 00:00:01 00:00:02 00:00:03 00:00:04 00:00:08 00:00:12 00:00:17
6
00:00:00 00:00:01 00:00:01 00:00:02 00:00:02 00:00:05 00:00:08 00:00:12
7
00:00:00 00:00:01 00:00:01 00:00:01 00:00:02 00:00:04 00:00:06 00:00:08
8
00:00:00 00:00:00 00:00:01 00:00:01 00:00:01 00:00:03 00:00:05 00:00:06
9
00:00:00 00:00:00 00:00:01 00:00:01 00:00:01 00:00:02 00:00:04 00:00:05
10
00:00:00 00:00:00 00:00:00 00:00:01 00:00:01 00:00:02 00:00:03 00:00:04
11
00:00:00 00:00:00 00:00:00 00:00:01 00:00:01 00:00:02 00:00:02 00:00:03
12
00:00:00 00:00:00 00:00:00 00:00:00 00:00:01 00:00:01 00:00:02 00:00:03
13
00:00:00 00:00:00 00:00:00 00:00:00 00:00:01 00:00:01 00:00:02 00:00:02
14
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:01 00:00:02 00:00:02
15
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:01 00:00:01 00:00:02