MOTUS®C14 Operating Instructions
Page
57
of
73
94 762 000 B
Revision 03.2022
English.
12.3 Error Acknowledgement
In case that a warning occurs, the connected load will continue to operate normally.
•
Warnings
cannot
be acknowledged.
•
As soon as the cause of a warning disappeared the warning will also disappear without
user interaction.
IMPORTANT:
Errors are leading to a load switch-off.
IMPORTANT:
The root cause of an error must be analyzed and fixed before
acknowledging the error.
•
An error can be acknowledged by pressing the main button for 2s, via a Analog Reset
Signal or via IO-Link.
Reset to Factory Settings
•
It is possible to reset the device setting to factory defaults using the ServiceTool or the
Display.
Nominal current
– Tripclass Combinations, 2,6 A
Nominal
current
TC 2E
TC 3E
TC 5
TC 10A
TC 10
TC 20
TC 30
TC 40E
0,1 A
X
X
X
X
X
X
X
X
0,2 A
X
X
X
X
X
X
X
X
0,3 A
X
X
X
X
X
X
X
X
0,4 A
X
X
X
X
X
X
X
X
0,5 A
X
X
X
X
X
X
X
X
0,6 A
X
X
X
X
X
X
X
X
0,7 A
X
X
X
X
X
X
X
X
0,8 A
X
X
X
X
X
X
X
X
0,9 A
X
X
X
X
X
X
X
X
1,0 A
X
X
X
X
X
X
X
X
1,1 A
X
X
X
X
X
X
X
X
1,2 A
X
X
X
X
X
X
X
X
1,3 A
X
X
X
X
X
X
X
X
1,4 A
X
X
X
X
X
X
X
X
1,5 A
X
X
X
X
X
X
X
X
1,6 A
X
X
X
X
X
X
X
X
1,7 A
X
X
X
X
X
X
X
X
1,8 A
X
X
X
X
X
X
X
X
1,9 A
X
X
X
X
X
X
X
X
2,0 A
X
X
X
X
X
X
X
O
2,1 A
X
X
X
X
X
X
X
O
2,2 A
X
X
X
X
X
X
X
O
2,3 A
X
X
X
X
X
X
X
O
2,4 A
X
X
X
X
X
X
X
O
2,5 A
X
X
X
X
X
X
O
O
2,6 A
X
X
X
X
X
X
O
O
X
Allowed Combination
O
Restricted Combination
i
!
!