Technical Data WSC 304 01

 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

Diagnosis / battery monitoring: 

 

Battery charge: 

Charging voltage 27.6V to 28V. Charging current limited to approx. 500mA. 
Short-circuit monitoring of the connection cables, charging voltage disconnected in the event of a short-circuit. 

 

Malfunction Function 

Diagnosis 

Yellow battery – LED flashes 

Mains failure or charging voltage 
below 25V 

Check the mains fuse and the 
charging voltage 

Yellow battery – LED is lit 

No battery or battery voltage below 
18V 

Check battery, battery voltage and 
battery fuse 

 

Note: The battery malfunction indicator can have a time delay of approx. 8 s. 

 
 
 

Note: 
Replace the emergency power batteries every 4 years! 

 

 
Optional plug-in modules: 

 

Multi-input malfunction warning module (WSA 301) – Model 1: 

Multi-input malfunction warning: 
1 x change-over contact (max. load: 60V, 1A) with 3 pole connection terminal for potential free transmission 
to the BMS / panel etc. 
2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded control centres 
to the break glass unit connected to the master smoke control unit.  

 

Alarm message: 
1 x change-over contact (max. load: 60V, 1A) with 3 pole connection terminal for potential free transmission 
to BMS / panel etc., or as monitored 2 wire alarm cable for cascading control centres. 

 

Jumper plugged in J1 = Only for the alarm transmission to the next smoke control panel unit (cascading). 
Jumper plugged in J2 = pot.-free alarm contact (factory setting). 
 

 

Wind/rain relaying module (WSA 302) – Model 2: 

1 x change-over contact (max. load: 60V, 1A) with 3 pole connection terminal for potential free transmission 
of the wind/rain trip. 

 
 

Ventilation time module (WSA 303) – Model 3: 

Automatic closing in the ventilation mode according to preselected time (1 min. to 30 min.) 
after ventilation OPEN was actuated. 
 

 

Installation information: 

Fit the break glass units at a height of approx. 1.40 m of FF top edge. 
 
 
 
 
 
 
 
 

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: