Cable lengths table 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

10 

 

Ensure that the electrical cables are always routed according to the valid national and local regulations of the individual 
country. 

 

Maintaining the cable functions 

The sample cable system directive (MLAR) in its current version is decisive for the type of cables and their corresponding 
way of routing. In most of the German provinces, MLAR has been introduced as Technical Construction Regulation. 
Various revisions of the MLAR as Technical Construction Regulation are valid in the individual provinces. Due to the fact 
that the requirements with regard to the conductors for smoke control systems contained in the individual versions differ 
considerably, different conductor requirements result for the individual provinces. MLAR is based on the state-of-the-art of 
the year 2000 (Revision: 06/2001). In this directive, for the first time a differentiation is made between machine operated 
and natural smoke ventilation systems. For natural smoke extraction systems it is sufficient to maintain the function 
according to classification E30. These cables must be checked and approved in accordance with DIN 4102 Part 12. Route 
the cables in conformity with the instructions of the cable manufacturers using the corresponding fastening materials. 
The maintenance of the function for the smoke ventilation cables is not required if all cable paths are monitored by the 
smoke detector and when the smoke and heat detection system opens as a result of the automatic detector tripping. 
 
Concealed installation is not an approved type of installation to maintain the function in accordance with DIN 4102 Part 12. 
The function is also only securely maintained by cables of class E30, or the room is monitored by smoke detectors. 
 
The cable network for smoke ventilation systems („Cable system“) ends at the interface (junction box) for the actuator! 
The flexible, heat resistant connection cable of the smoke ventilation system actuator is part of the system component 
‚electric motor actuation' and does not belong to the electrical installation! 
 

We recommend in all cases to discuss the type of cable routing with the competent fire fighting authorities. 
Independent of the fact whether or not the respective MLAR is introduced in the corresponding province as 
Technical Building Regulation, we recommend to point out the technical possibilities and the state-of-the-art of 
MLAR 2000. 

 

Cable length table 

 

For determining the maximum permissible cable lengths between the smoke control unit and the actuators, taking into 
account the specified cables cross sections, please refer to the following table: 

 

Maximum motor current:  

4A  

(

Note:

 Be aware of the overall capacity of the smoke control unit!) 

 

Maximum cable length: (always routed from the central smoke control unit to the last junction box) 
Actuating current: Sum of all motor currents per group module 

 

Note:  

Do not use the green/yellow wire! 

 

Per motor supply line, 3 wires are required ( 2 wires current carrying /1 wire for monitoring ) 

 

 

Cross section 

3 wire 

5 wire 

3 wire 

5 wire 

3 wire 

 

1,5 mm² 

1,5 mm² 

2,5 mm² 

2,5 mm² 

4 mm² 

Actuator current in 
Amps 

 

(2 wires in 

parallel) 

 

(2 wires in 

parallel) 

 

84,00 m 

168,00 m 

140,00 m 

280,00 m 

224,00 m 

42,00 m 

84,00 m 

70,00 m 

140,00 m 

112,00 m 

28,00 m 

56,00 m 

46,67 m 

93,33 m 

74,67 m 

21,00 m 

42,00 m 

35,00 m 

70,00 m 

56,00 m 

(The information is valid for ambient temperatures of 25°C) 
 

Formula for the calculation of the maximum cable length 

Permissible max. voltage drop in the line UL :  2 Volt 

 
 
max. cable length = permissible voltage drop(

UL

) x conductivity of copper(

56

) x cable cross section(

A

 

 

   

max. actuator current total (

I

) in amps 

x 2

 

 
Permissible cable length for the break glass unit supply cable when using......4x2x0.8mm:     

up to 200m

 

 
The motor connection cable length to the junction box (or control module) must not exceed 

10 m

 

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: