Safety information WSC 304 01 

__________________________________________________________________________ 

Smoke control unit - WSC 304 01 

 

Only allow correspondingly trained, qualified 
and skilled personnel to carry out installation work. 

Reliable operation and the avoidance of 
damage and hazards is only guaranteed if 
installation and settings are carried out carefully
in accordance with these instructions. 

Check the technical data on the system plate. 

Hazards to persons ensuing from flaps and 
wings operated by electric motors. 

The forces occurring in the automatic mode can 
be such that parts of the body could get crushed. 
When opened, actuators could protrude into the 
room. 
For this reason, measures have to be taken
prior to starting up the actuators which exclude 
the danger of injury. 

With wings tilting inwards or outwards, the wing 
must be protected from hinging down once the 
actuator is unhooked (e.g. for window cleaning). 
For safety reasons we recommend the use of 
catching shears. 

In the event that wings or flaps are subjected to 
high wind loads, we recommend to connect the 
central control unit to a wind detector which will 
automatically close the flaps. 

The fastening methods are exclusively intended 
for the intended use for which they are designed
The manufacturer does not assume any liability 
for possible damage resulting from inappropriate 
use. 

Can cause death, severe injury or considerable 
damage to assets. 
The connection of the control system is reserved 
for qualified personnel. 
Disconnect all poles of the unit from the supply 
voltage prior to opening, installation or 
assembling. Adhere to the VDE regulations.

230V AC  dangerous voltage 

 

 

Field of application 

Maintenance work 

Cable routing and electrical connection 

Leave the insulation of the power supply 

cable in place up to the mains terminal. 

Manufacturer's declaration 

The central control system is exclusively designed 
for the automatic closing of smoke extraction 
systems, windows, flaps or doors. 
Always check that your system meets the valid 
regulations. 
Pay particular attention to the opening cross section, 
the opening time and opening speed. The cable cross
 sections depend on the cable length and current 
consumption (amperage). 

Where devices are used in smoke and heat 
extraction systems, ensure that they are checked, 
maintained and, if necessary, repaired at least once 
per year.
Remove all soiling from the devices, 
check the fastening and clamping screws for firm 
seating. Trial run the entire system. 
Defective devices may only be repaired in our factory
Only use original spare parts. 
The supplied accumulators are subject to regular 
checks and must be replaced every 4 years. 

Fuse the 230V AC power supply cable separately on 
site. 

Adhere to the DIN and VDE regulations (Germany) 
or equivalent in your country. 
Establish the cable types, if necessary, with the local 
approval bodies or the fire protection authority. 
Do not conceal flexible cables. Junction box 
must be accessible for maintenance purposes. 
Disconnect all poles of the mains voltage and the
accumulators prior to starting maintenance work or 
making changes to the system. 
Secure the system to prevent unintentional switching 
on again. 
Design cable types, lengths and cross sections in 
accordance with the technical information. 
Route all low voltage cables (24V DC) separate from 
the power current cables. 

The devices have been inspected and manufactured 
in accordance with the European directives. 
A corresponding manufacturer's declaration is 
available. 
You are only authorised to use the devices if a 
conformity declaration is issued for the entire system. 

 

Attention!

Adherence to the following information is mandatory:

 

 

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: