Window Master WSC 304 01 Скачать руководство пользователя страница 15

Commisioning WSC 304 01 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

15 

 

When error message occur, please refer to chapter Operating elements and fuse review.

An acoustic message only occurs in the Break glass unit with the door closed or the door contact switch 
pressed!

1)

2)

Adhere to the relevant regulations! Externally disconnect the mains voltage.

3)

4)

a) Closely observe the actuators during opening and closing. They must not be impaired in any 

position by the building structure. Also the motor connection cables 
must not be subject to pulling or crushing.

5)

6)

The control centre is completely installed, without the operating voltage applied

only

With mains voltage, without accumulator

With mains voltage, with accumulator

Ventilation button

Break glass unit

Break glass unit (secondary)

a) Check all mechanical and electrical components for damage.
b) Check the DIP slide switches in the control centre for their correct (required) position.
c) Check all screw and plug connections for tightness and/or firm seating.
d) Check that all external components are installed.

Actuators:

Is the final module at the last or only actuator inserted?

Automatic detectors:

Is the active end module at the last or only detector inserted?

Manual detectors:

Is the jumper 

 inserted in the last or only operating panel?

a) Connect the mains cables and reapply the mains voltage.
b) The mains LED is ON, the operating LED is OFF, the accumulator LED is ON. The malfunction message at 

the operating panels is ON.

 

a) Remove the protection film of the lateral adhesive tape for the 1.9 Ah battery, and firmly press the two 

batteries together according to the picture (next page).

b) Remove the protection film from one face of the supplied foam rubber. Glue each foam rubber to the 

bottom side of the accumulators. Connect the accumulators to the black accumulator bridge according to 
the wiring diagram, then connect the red and the blue connection cable to the red and the black flat plug. 
Remove the bottom protection film of the foam rubber and insert the batteries in the control unit according 
to figure 1, and firmly press down to the housing bottom!

c) Plug the red connection cable to the + and the blue connection to the  flat plug of the control unit. Note: 

Check correct polarity!

d) The operating LED is ON, the accumulator LED is OFF. The malfunction message at the operating panels 

is OFF.

b) Briefly actuate the Open button to have the actuators move open up to the final position. With the SW2/2 

=ON (hold-to-run) setting, the actuators only move as long as the button is pressed. The OPEN display (if 
existing) in the button is ON.

c)

Briefly actuate the CLOSED button, the actuators close. The Open display is OFF.

d) Press both buttons simultaneously while running, this corresponds to stop. The ventilation Open display is 

ON, the actuators stop.

e) Briefly press the Closed button again, the actuators fully close, the Open display is OFF.

a) Open the door and press the red Open button. The actuators move open through to the end position. The 

red alarm LED (also in the control unit) is ON, at the same time a permanent acoustic signal sounds (door 
contact pressed!).

b) While running, press the Closed button at the ventilation button, then press both buttons, the actuators 

must neither close nor stop!

c) Press the reset/Closed button in the break glass unit. The actuators close through to the end position. The 

ventilation function is released again. The red alarm LED (also in the control unit) and the signal generator 
are OFF.

a) Check as described under 5). „Operation“, „Malfunction“ and the acoustic signal are missing!

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: