Installation WSC 304 01

 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

 

Cable routing 

 
Observe the safety information on page 2. 
For cable routing we recommend the use of fire protected cables retaining their function E90 or E30. 
However, this has to be agreed with the Engineer or, if necessary, with the local fire protection department. 
Do not reduce the cable cross sections specified in the cable lengths table. 
All cables of the control centre (except the mains supply cable) carry 24V DC and have to be routed separate 
from the mains supply cable. 
Adhere to the pertinent VDE regulations when routing the cables. 
Do not use the green/yellow conductor. 
Ensure that the mains cable can be switched via an external or customer-supplied two-pole switch element or 
a switch element controlling all poles. 
 

Control centre installation 

 
Note that the control centre has to be installed in a dry room.  
 
Concealed housing 
Refer to the sketch below for the installation position 

 

Open central control and remove the housing 
top section (door) from the housing bottom section. 
Fasten the housing bottom section in the wall cut-out 
(cut-out dimension 335 x 350 x 95) and 
refit the housing top section. 
Also possibility for surface mounting with the included frames. 
 
 

Installation of the Break glass unit, ventilation buttons and detectors 

 
Ensure that the Break glass unit and the ventilation buttons are visible and well accessible. Do not fit behind 
protruding walls, door panels or hidden by the building structure. 
Note: Installation height of the Break glass unit = 1.4 m above floor top edge. 
Install the automatic detectors in accordance with the enclosed operating manuals. 
 

Installation 

 
Lead the connection cables into the housing of the control centre from above. 
All connection terminals (except the mains terminals) are of the plug-on type. 
Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made 
correctly. 
 
Incorrect clamping, mixing up numbers or colours could lead to malfunctions of the central control or of the 
external components. 
 

Notice:

  

Smoke central units in metal housing 
are only for surface mounting. 

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: