Technical function description WSC 304 01 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

 
Smoke and heat extraction system alarm trip: 

 

Break glass unit:

Break the glass in the break glass unit! Press the red button. The smoke extraction opens. 
An acoustic alarm signal sounds (continuous sound) in the break glass unit. 
All ventilation functions are out of operation. 

Display:

 The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit. 

 

Smoke detector: 

If smoke develops, the smoke extraction system automatically opens. 
An acoustic alarm signal sounds (continuous sound) in the break glass unit. 
All ventilation functions are out of operation. 

Display:

 The red alarm LED in the smoke control unit, the red LED in the break glass unit, and the red LED at 

the tripped automatic detector are lit. 
 

Resetting a tripped smoke control unit: 

Press the „CLOSE button“ in the break glass unit or the „Reset button” in the smoke control unit. 
The acoustic alarm signal in the break glass unit stops sounding. 
The ventilation functions are operational again once the smoke extraction system has closed. 
(Prior to resetting, blow out or replace the detector after it was tripped by an automatic detector). 

Display:

 The red alarm LED in the smoke control unit, the red LED in the break glass unit, and the red LED at 

the tripped automatic detector extinguish. 
 

Tripping caused by high temperature: 

The smoke control system automatically trips if the temperature inside the smoke control unit exceeds 70°C. 
An acoustic alarm signal sounds (continuous sound) in the break glass unit. 

Display:

 The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit. 

               The yellow malfunction

 

LED in the break glass unit flashes. 

 

Resetting a trip caused by high temperature: 

The smoke extraction system can be closed again by pressing the „Reset button“ in the smoke control unit or 
the „CLOSE button“ in the break glass unit. 
After operating the CLOSE function, an acoustic pulse tone sounds, and the flashing malfunction LED is only 
displayed in the break glass unit. The green operation LED remains lit as a special fault diagnosis. 
Operating the ventilation button, OPEN or STOP will lead to the tripping

 

of another alarm. 

 

Note: 

The built-in thermal switch will then be irreversibly destroyed. The smoke control unit has to be returned for 
checking.  
 

Alarm trip caused by a malfunction signal:  

When this function is activated (SW2/1 = ON), the smoke control unit will trip

 

in the event of a motor, smoke 

detector or break glass unit circuit malfunction. An acoustic alarm signal sounds (continuous sound) in the 
break glass unit. 
No trip occurs as a result of a malfunction in the mains or battery circuit. 

Display:

 The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit. 

               The yellow malfunction LED in the break glass unit and the corresponding yellow malfunction  
               LED in the smoke control unit flash. 
 

Option: External signalling of the alarm or malfunction signal 

It is possible to send an alarm or malfunction signal potential free, by plugging in the alarm/malfunction 
signalling module. 
 

Cascading smoke control units: 

The smoke control units can be cascaded by a monitored 2 wire connection from the alarm module of the 
master smoke control unit to the smoke detector input of the slave central panel. 
A malfunction in the cascaded smoke control units is detected via the 2 wire BUS cable. The malfunction is 
only displayed in the corresponding smoke control unit and in the break glass unit connected to the master 
smoke control unit. 
 

 
 

Содержание WSC 304 01

Страница 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Страница 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Страница 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Страница 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Страница 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Страница 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Страница 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Страница 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Страница 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Страница 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Страница 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Страница 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Страница 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Страница 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Страница 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Страница 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Отзывы: