3
088-00
60706-207
DC ELECTRICAL
INTERCONNECTION
**** CAUTION ****
Never run the AC and DC wiring in the same con-
duit.
ASCO 185 UL SWITCH
Your DC connection points in the ASCO 85 UL ATS
are on the terminal block on the bottom of the con-
troller in the lower left hand corner of the ATS panel.
The terminal block (TB7) is numbered through
9. These terminals will accept # 22 - # 4 AWG
stranded wire. It is recommended that you use # 6
AWG for distances up to 200 feet. You need to run
two (2) wires from the engine generator set to the
transfer switch. You will be using terminals 4 and 5,
wire Start # 23 will connect to terminal # 5 and wire
Battery Negative # will connect to terminal # 4.
See table and illustration below.
WIRE #
PURPOSE
RECOMMENDED
COLOR
# 23
Start
Black
# 1
Battery Negative
White
INITIAL START UP
******************
***** WARNING *****
******************
DO NOT jump start these engine generator sets.
Starting these units on a low battery of jump start-
ing them will cause damage to the engine control
module.
Use the following checklist to verify correct in-
stallaion before starting the engine:
�
Engine oil.* Check level & fill as required with
proper grade/quantity.
�
Unit mounting base properly bolted down.
�
Clearance for service and maintenance on all
sides.
�
Proper fuel line material and size.
�
All fuel line connections tight.
�
Fuel line protected and a moisture trap in
stalled (may be required for NG).
�
LP/NG pressure OK. 4-6 oz. (7- in. WC).
�
Battery connections clean and tight.
�
Battery fully charged.
�
All AC and DC wiring installed and properly
protected.
* Refer to engine owners manual for proper
levels and types.
After completing the above checklist, the engine
generator set is ready for the initial start-up test.
225 S. CORDOVA AVE.
LECENTER, MN 56057
507-357-6821
SERVICE DEPT.
507-357-6831
Содержание ULPSS15B2E
Страница 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...
Страница 10: ...11088 00 10 60706 207...
Страница 18: ...11088 00 18 60706 207...
Страница 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...
Страница 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...
Страница 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...
Страница 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...
Страница 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...