Transfer Switch & Engine Generator

Automatic (remote) Operation

This procedure checks the electrical operation of 

the automatic transfer switch.  If the actual operation 

does not follow this procedure, consult the trouble-

shooting section in the transfer switch manual.

    .  Turn on the preferred source (utility) circuit 

breaker.  The 

Utility Acceptable Light

 should now 

come on as well as the 

Load On Utility Light

.  If 

these lights fail to come on recheck your incoming 

power to insure you have 240 volts nominal.  If not, 

troubleshoot your utility source before continuing.

    

2.  Press and release the 

Auto button

 on the 

engine control module (ECM).  The auto mode icon 

will appear on the screen.  The unit is now ready to 

be operated from the Automatic Transfer Switch.

    3.  Turn on the alternate source (generator) circuit 

breaker.

     ******************

*****  WARNING  *****

     ******************

PERSONAL INJURY HAZARD - Install front cover 

in transfer switch before operation.  An electrical sys-

tem fault could cause a flash and severe personal 

injury.

DESCRIPTION

The digital controller provides sensing, timing, and 

control functions for the ATS.  This micro-processor-

based controller includes built-in control buttons and 

status lights for control of the ATS and the generator.

PUSH BUTTONS

On the front control display are three push buttons 

that control the operation of the generator and the 

ATS.

****  CAUTION  ****

Before using the transfer test button, be sure 

that conditions are safe for running the genera-

tor and for load transfer

TRANSFER TEST    

Use this button to test the 

system.  This operation starts the generator and 

transfers the load.  The controller is shipped with a 

load transfer set by default.  Changing the exercise 

without a load will be discussed later.  Be sure that 

conditions are safe to do this operation.

BYPASS TIME DELAY    

Use this button to cancel 

the active time delay or exercise period (stops the 

generator after cooldown).

SET ENGINE EXERCISER    

Use this button to set 

the automatic exerciser.

INDICATOR LIGHTS

On the front control display are five lights that indi-

cate the status of the sources and the ATS.

UTILITY ACCEPTABLE    

This light indicates that 

the utility voltage is acceptable for connection to the 

load.

GENERATOR ACCEPTABLE    

This light indicates 

that the generator voltage and frequency is accept-

able for connection to the load.

LOAD ON UTILITY    

This light indicates that the 

generator voltage is acceptable for connection to the 

load.

LOAD ON GENERATOR    

This light indicates that 

the generator voltage and frequency is acceptable 

for connection to the load.

ASCO 185 DIGITAL CONTROLLER

Содержание ULPSS15B2E

Страница 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...

Страница 2: ...l Pressure Tables 8 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 12 DC Electrical Connections 13 INITIAL START UP 1...

Страница 3: ...ground rod driven into the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Keep fuel containers out of reach of children b Do not smoke or use open flame...

Страница 4: ...r inside or outside instal lation The transfer switch is UL1008 approved A seven day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure...

Страница 5: ...sfer switch The installation must comply with all national state and local codes Before beginning the installation process check the rating of the generator set and its transfer switch rating Be certa...

Страница 6: ...to the fuel solenoid on the unit must be four to six ounces psi per square inch or 7 to 11 inches W C water column These fuel pressures are critical failure to provide the proper pressure can cause ma...

Страница 7: ...led FEET SIZE OF PIPE up to 25 FT 3 4 Pipe 25 100 FT 1 Pipe over 100 FT Consult Factory Allow an additional 3 feet for each standard elbow Do not use street ells restrictive WARNING PERSONAL DANGER Do...

Страница 8: ...ed LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit Celsius TANK TEMPERATURE TANK SIZE 60 F 16 C 150 GALLON 32 F 0 C 250 GALLON 0 F 18 C 500 G...

Страница 9: ...disconnect the nega tive cable first and then the positive cable 5 Be sure all connections are tight and coat the terminals and cable ends with dielectric grease WARNING The electrolyte is a diluted s...

Страница 10: ...11088 00 10 60706 207...

Страница 11: ...that this circuit be fused for 15 amps Terminal block connections have been provided in the customer connection area of the engine generator set See Page 10 for diagram NOTICE The battery tender is no...

Страница 12: ...are removed from main distribution panels and reinstalled in the emer gency distribution panel Suggested circuits freez er refrigerator furnace emergency lights sump pump emergency outlet circuits etc...

Страница 13: ...ative White INITIAL START UP WARNING DO NOT jump start these engine generator sets Starting these units on a low battery of jump start ing them will cause damage to the engine control module Use the f...

Страница 14: ...ote start WILL NOT occur AUTO White Button This button places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will moni...

Страница 15: ...l block in the ATS The voltage should be 240 volts plus or minus nominal The frequency should be between 61 5 to 62 hertz Hz The voltage should also be checked between the hot terminals L2 and L6 and...

Страница 16: ...s for control of the ATS and the generator PUSH BUTTONS On the front control display are three push buttons that control the operation of the generator and the ATS CAUTION Before using the transfer te...

Страница 17: ...ctuator Actuator Position clock battery off S2 10 on up off down exerciser off S1 7 on up off down with load or without load without load S1 8 with up without down SETTING THE EXERCISER CIRCUIT Press...

Страница 18: ...11088 00 18 60706 207...

Страница 19: ...s 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the button The value begins to flash Press 4 or 3 to adjus...

Страница 20: ...ule detects that the engine oil temperature has exceeded the high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the unde...

Страница 21: ...MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type of mainte...

Страница 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...

Страница 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...ked up engine generator set 9 Defective starter fuel solenoid relay s ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Def...

Страница 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 28: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some...

Отзывы: