background image

088-00

20

60706-207

DSE 3110 CONTROL

FAULT CODES

DESCRIPTION

AUXILIARY INPUTS

Auxiliary inputs can be user configured and will display 

the message as written by the user. 

FAIL TO START

The engine has not fired after the preset number of start 

attempts

FAIL TO STOP

The module has detected a condition that indicates that 

the engine is running when it has been instructed to stop.

NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor 

- If engine is at rest check oil sensor wiring and configuration.

LOW OIL PRESSURE

The module detects that the engine oil pressure has fallen 

below the low oil pressure pre-alarm setting level after the 

Safety On

 timer has expired.

ENGINE HIGH OIL 

TEMPERATURE

The module detects that the engine oil temperature has 

exceeded the high engine temperature pre-alarm setting 

level after the 

Safety On

 timer has expired.

UNDERSPEED

The engine speed has fallen below the underspeed pre 

alarm setting

OVERSPEED

The engine speed has risen above the overspeed pre 

alarm setting

BATTERY UNDER 

VOLTAGE / BATTERY 

OVER VOLTAGE

The DC supply has fallen below or risen above the low/

high volts setting level.

GENERATOR UNDER 

VOLTAGE

The generator output voltage has fallen below the pre-set 

pre-alarm setting after the 

Safety On

 timer has expired.

GENERATOR OVER 

VOLTAGE

The generator output voltage has risen above the pre-set 

pre-alarm setting.

GENERATOR UNDER 

FREQUENCY

The generator output frequency has fallen below the 

pre-set pre-alarm setting after the 

Safety On

 timer has 

expired.

GENERATOR OVER 

FREQUENCY

The generator output frequency has risen above the pre-

set pre-alarm setting.

C

D

Содержание ULPSS15B2E

Страница 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...

Страница 2: ...l Pressure Tables 8 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 12 DC Electrical Connections 13 INITIAL START UP 1...

Страница 3: ...ground rod driven into the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Keep fuel containers out of reach of children b Do not smoke or use open flame...

Страница 4: ...r inside or outside instal lation The transfer switch is UL1008 approved A seven day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure...

Страница 5: ...sfer switch The installation must comply with all national state and local codes Before beginning the installation process check the rating of the generator set and its transfer switch rating Be certa...

Страница 6: ...to the fuel solenoid on the unit must be four to six ounces psi per square inch or 7 to 11 inches W C water column These fuel pressures are critical failure to provide the proper pressure can cause ma...

Страница 7: ...led FEET SIZE OF PIPE up to 25 FT 3 4 Pipe 25 100 FT 1 Pipe over 100 FT Consult Factory Allow an additional 3 feet for each standard elbow Do not use street ells restrictive WARNING PERSONAL DANGER Do...

Страница 8: ...ed LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit Celsius TANK TEMPERATURE TANK SIZE 60 F 16 C 150 GALLON 32 F 0 C 250 GALLON 0 F 18 C 500 G...

Страница 9: ...disconnect the nega tive cable first and then the positive cable 5 Be sure all connections are tight and coat the terminals and cable ends with dielectric grease WARNING The electrolyte is a diluted s...

Страница 10: ...11088 00 10 60706 207...

Страница 11: ...that this circuit be fused for 15 amps Terminal block connections have been provided in the customer connection area of the engine generator set See Page 10 for diagram NOTICE The battery tender is no...

Страница 12: ...are removed from main distribution panels and reinstalled in the emer gency distribution panel Suggested circuits freez er refrigerator furnace emergency lights sump pump emergency outlet circuits etc...

Страница 13: ...ative White INITIAL START UP WARNING DO NOT jump start these engine generator sets Starting these units on a low battery of jump start ing them will cause damage to the engine control module Use the f...

Страница 14: ...ote start WILL NOT occur AUTO White Button This button places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will moni...

Страница 15: ...l block in the ATS The voltage should be 240 volts plus or minus nominal The frequency should be between 61 5 to 62 hertz Hz The voltage should also be checked between the hot terminals L2 and L6 and...

Страница 16: ...s for control of the ATS and the generator PUSH BUTTONS On the front control display are three push buttons that control the operation of the generator and the ATS CAUTION Before using the transfer te...

Страница 17: ...ctuator Actuator Position clock battery off S2 10 on up off down exerciser off S1 7 on up off down with load or without load without load S1 8 with up without down SETTING THE EXERCISER CIRCUIT Press...

Страница 18: ...11088 00 18 60706 207...

Страница 19: ...s 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the button The value begins to flash Press 4 or 3 to adjus...

Страница 20: ...ule detects that the engine oil temperature has exceeded the high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the unde...

Страница 21: ...MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type of mainte...

Страница 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...

Страница 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...ked up engine generator set 9 Defective starter fuel solenoid relay s ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Def...

Страница 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 28: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some...

Отзывы: