DSE 3110 ENGINE CONTROL

PROTECTIONS

When an alarm is present, the Common alarm LED 

if configured will illuminate.  

The LCD display will 

show an icon to indicate the failure.

WARNINGS

Warnings are non-critical alarm conditions and do 

not affect the operation of the generator system, 

they serve to draw the operators attention to an un-

desirable condition.  Warning alarms are self-reset-

ting when the fault condition is removed.  The icon 

will appear steady in the display.

SHUTDOWNS

Shutdowns are critical alarm conditions that stop the 

engine and draw the operator’s attention to an un-

desirable condition.  Shutdown alarms are latching.  

The fault must be removed and the STOP/RESET 

button pressed to reset the module.  

The icon will 

appear flashing in the display.

MODULE DISPLAY

TIMER ICON

When the module is controlling the engine (start-

ing and stopping) an animated timer icon will be 

displayed in the icon area to indicate that a timer is 

active, for example cranking time, crank rest, etc.

STOPPED ICON

When there are no alarms present, an icon will be 

displayed to indicate the engine is stopped and what 

mode the unit is in.

  Stop Mode           Auto Mode            Manual Mode

RUNNING ICON

When there are no alarms present, an animated icon 

is displayed to indicate the engine is running.

USB ICON

When a USB connection is made to the module the 

USB icon is displayed.

MEMORY CORRUPTION

If either the config file or engine file becomes cor-

rupted the unit will display the following icon.

PREVENTIVE

MAINTENANCE

Reasonable care in preventive maintenance will 

insure high reliability and a long life for the engine 

generator set and Automatic Transfer Switch.

     *****************

*****  WARNING  *****

     *****************

When performing any type of maintenance on this 

equipment make sure the selector switch on the en-

gine generator is in the off position.  If you are work-

ing in the Automatic Transfer Switch, confirm with a 

reliable meter that all power has been disconnected.

AUTOMATIC TRANSFER SWITCH

Clean and inspect the switch once a year.  de-ener-

gize all power sources, both line and engine genera-

tor set, then brush and vacuum away any excessive 

dust or dirty accumulation.  You can at this time with 

the contactor de-energized remove the contactor 

covers and check the contacts.  Make sure contacts 

are clean and not burned or pitted.

ENGINE GENERATOR SET

Service the engine in accordance with the engine 

manufacturers manual provided with your new 

equipment.  Routinely remove debris and dirt from 

around the inside generator enclosure.  Insure that 

the air intakes are free from leaves and other debris 

at all times.

Clean and inspect battery terminals a least twice a 

year.  Check the battery water level at least twice a 

year also.

Other than keeping the generator clean and free of 

debris there is no other routine or preventative main-

tenance required, as long as the generator is run 

biweekly to keep it dry and in good working order.

COLD WEATHER OPERATION

Extreme cold weather operation requires special 

considerations.  Higher CCA batteries are required 

for cold weather starting, 650 CCA or larger are rec-

ommended.  In addition you should consider install-

ing an oil heater kit and a battery warmer for reliable 

starting during cold weather.

 

Содержание ULPSS15B2E

Страница 1: ...11088 00 60706 207 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS15B2W E...

Страница 2: ...l Pressure Tables 8 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 12 DC Electrical Connections 13 INITIAL START UP 1...

Страница 3: ...ground rod driven into the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Keep fuel containers out of reach of children b Do not smoke or use open flame...

Страница 4: ...r inside or outside instal lation The transfer switch is UL1008 approved A seven day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure...

Страница 5: ...sfer switch The installation must comply with all national state and local codes Before beginning the installation process check the rating of the generator set and its transfer switch rating Be certa...

Страница 6: ...to the fuel solenoid on the unit must be four to six ounces psi per square inch or 7 to 11 inches W C water column These fuel pressures are critical failure to provide the proper pressure can cause ma...

Страница 7: ...led FEET SIZE OF PIPE up to 25 FT 3 4 Pipe 25 100 FT 1 Pipe over 100 FT Consult Factory Allow an additional 3 feet for each standard elbow Do not use street ells restrictive WARNING PERSONAL DANGER Do...

Страница 8: ...ed LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit Celsius TANK TEMPERATURE TANK SIZE 60 F 16 C 150 GALLON 32 F 0 C 250 GALLON 0 F 18 C 500 G...

Страница 9: ...disconnect the nega tive cable first and then the positive cable 5 Be sure all connections are tight and coat the terminals and cable ends with dielectric grease WARNING The electrolyte is a diluted s...

Страница 10: ...11088 00 10 60706 207...

Страница 11: ...that this circuit be fused for 15 amps Terminal block connections have been provided in the customer connection area of the engine generator set See Page 10 for diagram NOTICE The battery tender is no...

Страница 12: ...are removed from main distribution panels and reinstalled in the emer gency distribution panel Suggested circuits freez er refrigerator furnace emergency lights sump pump emergency outlet circuits etc...

Страница 13: ...ative White INITIAL START UP WARNING DO NOT jump start these engine generator sets Starting these units on a low battery of jump start ing them will cause damage to the engine control module Use the f...

Страница 14: ...ote start WILL NOT occur AUTO White Button This button places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will moni...

Страница 15: ...l block in the ATS The voltage should be 240 volts plus or minus nominal The frequency should be between 61 5 to 62 hertz Hz The voltage should also be checked between the hot terminals L2 and L6 and...

Страница 16: ...s for control of the ATS and the generator PUSH BUTTONS On the front control display are three push buttons that control the operation of the generator and the ATS CAUTION Before using the transfer te...

Страница 17: ...ctuator Actuator Position clock battery off S2 10 on up off down exerciser off S1 7 on up off down with load or without load without load S1 8 with up without down SETTING THE EXERCISER CIRCUIT Press...

Страница 18: ...11088 00 18 60706 207...

Страница 19: ...s 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the button The value begins to flash Press 4 or 3 to adjus...

Страница 20: ...ule detects that the engine oil temperature has exceeded the high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the unde...

Страница 21: ...MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type of mainte...

Страница 22: ...11088 00 22 60706 207 ENGINE GENERATOR SET LAYOUT ULPSS15B2W E...

Страница 23: ...23 11088 00 60706 207 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...ked up engine generator set 9 Defective starter fuel solenoid relay s ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Def...

Страница 25: ...25 11088 00 60706 207 AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...11088 00 26 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 27: ...27 11088 00 60706 207 MAINTENANCE LOG DATE HOURS ITEM WORK PERFORMED...

Страница 28: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some...

Отзывы: