OPM-117/B

SPECIFICATIONS

PSS60/E

LP Gas

Wattage

56,000

60,000

60,000

60,000

Volts

120/240

120/208

120/240

277/480

kvA

56

75

75

75

Phase

Single

Three

Three

Three

Amps

233

208

180

90

CB Size

250

200

200

90

Hertz

60

60

60

60

Natural Gas
Wattage

55,000

58,000

58,000

58,000

Volts

120/240

120/208

120/240

277/480

kvA

55

72

72

72

Phase

Single

Three

Three

Three

Amps

229

201

174

87

CB Size

250

200

200

90

Hertz

60

60

60

60

Engine

Model

GM 5.7L

Starting System

12 Volt

Muffler

Standard

Fuel Consumption (full load)

LP                                                           

NG                                                           

9.29 GAL/HR - 850,964 BTU/

HR

799 FT³/HR - 798,455 BTU/

HR

Generator Testing Resistance

Note: Review the Stamford Newage nameplate on your 

generator before selecting the correct information below.

Model 

   Stamford 

UCI224F1J

Winding Group   

06

Resistances:  

Rotor 

   0.83 

Ohms 

@20°C

Stator (L-L)   

 

0.012 Ohms Per Ph @ 20°C

Exciter Rotor (L-L) 

 

0.156 Ohms Per Ph @ 20°C

Exciter Stator (L-L)   

20.00 Ohms @ 20°C

Aux Winding 

 

 

2.6 Ohms @ 20°C

Voltage Regulator (L-l)  AS440

Model 

   Stamford 

UCI224F1L

Winding Group   

311

Resistances:

Rotor 

   0.83 

Ohms 

@20°C

Stator (L-L)   

 

0.033 Ohms Per Ph @ 20°C

Exciter Rotor (L-L) 

 

0.156 Ohms Per Ph @ 20°C

Exciter Stator (L-L)   

20.00 Ohms @ 20°C

Aux Winding 

 

 

2.6 Ohms @ 20°C

Voltage Regulator (L-L)  AS440

PSS90/E

LP Gas

Wattage

80,000

80,000

80,000

80,000

Volts

120/240

120/208

120/240

277/480

kvA

80

100

100

100

Phase

Single

Three

Three

Three

Amps

333

278

240

120

CB Size

350

300

300

150

Hertz

60

60

60

60

Natural Gas

Wattage

90,000

90,000

90,000

90,000

Volts

120/240

120/208

120/240

277/480

kvA

90

112

112

112

Phase

Single

Three

Three

Three

Amps

375

312

270

135

CB Size

350

300

300

150

Hertz

60

60

60

60

Engine

Model

GM 5.7L

Starting System

12 Volt

Muffler

Standard

Fuel Consumption (full load)

LP                                                         

NG                                                           

12.4 GAL/HR - 1,192,000 

BTU/HR

1,230 FT³/HR - 1,230,000 

BTU/HR

Generator Testing Resistance

Note: Review the Stamford Newage nameplate on your 

generator before selecting the correct information below.

Model 

   Stamford 

UCI274C1J

Winding Group   

06

Resistances:

Rotor 

   1.12 

Ohms 

@20°C

Stator (L-L)   

 

0.011 Ohms Per Ph @ 20°C

Exciter Rotor (L-L) 

 

0.156 Ohms Per Ph @ 20°C

Exciter Stator (L-L)   

20.0 Ohms @ 20°C

Aux Winding 

 

 

2.6 Ohms @ 20°C

Voltage Regulator (L-L)  AS440 

Model 

   Stamford 

UCI274C1L

Winding Group   

311

Resistances:  

Rotor 

   1.12 

Ohms 

@20°C

Stator (L-L)   

 

0.030 Ohms Per Ph @ 20°C

Exciter Rotor (L-L) 

 

0.156 Ohms Per Ph @ 20°C

Exciter Stator (L-L)   

20.0 Ohms @ 20°C

Aux Winding 

 

 

2.6 Ohms @ 20°C

Voltage Regulator (L-L)  AS440

Содержание PSS60-17

Страница 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Страница 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Страница 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Страница 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Страница 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Страница 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Страница 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Страница 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Страница 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Страница 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Страница 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Страница 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Страница 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Страница 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Страница 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Страница 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Страница 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Страница 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Страница 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: