OPM-117/B

INSTALLING THE BATTERY

CAUTION:

In the following battery installation procedure, check to be 

sure the selector switch remains in the ‘off’ position. This 

should be your last step before initial start-up.

A customer supplied twelve-volt battery is required to 

complete the 

installation. Installation of the highest CCA rated battery, 

within the 

correct BCI group (size), will increase cold weather starting 

performance. 

Gel batteries should not be used 

with the 

battery tender installed in the generator enclosure. 

 

Voltage  

BCI Group   

MIN. CCA Rating

        12 

 

              24   

 

 

   650

Installation and servicing of batteries must be performed 

or supervised only by persons knowledgeable of batteries 

and the required precautions. Keep unauthorized persons 

away from batteries. When installing or replacing batteries, 

use the proper group/size starting battery. The battery 

should be a maintenance free lead acid design. Deep cycle 

batteries

 will not work 

for this application. 

CAUTION: PERSONAL DANGER

NEVER dispose of a battery in a fire. The battery is capable 

of exploding.

DO NOT open or mutilate the battery. Released electrolyte 

is known to be harmful  to the skin and eyes and to be very 

toxic.

These generator sets are all 

NEGATIVE 

ground. Be very 

careful not to connect the battery in reverse polarity, as this 

may short circuit the battery charging system on the engine 

and damage electronic components.

CAUTION:

A battery presents a risk of electrical shock and high short 

circuit current. The following precautions must be observed 

when working with batteries. 

1. Remove watches, rings, and other metal objects.

2. Use tools with insulated handles.

3. Check both the battery cable ends and the battery posts 

  to be sure they are free of corrosion.

4. Always connect the battery positive cable first and then 

  connect the battery negative cable. When removing the 

  battery cables from the battery, reverse the procedure 

  and disconnect the negative cable first and then the 

  positive cable.

LUBRICATION & COOLANT

Before starting the engine, check the oil level in the 

crankcase. If it is low, refill to the full mark with the proper 

weight/grade of oil as recommended by the engine 

manufacturer’s maintenance instructions. The necessity of 

using the correct oil and keeping the crankcase full cannot 

be over emphasized. Failure to do so will cause excessive 

engine wear and shorten its useful life. 

Before starting the engine, Check the coolant level in 

the radiator. If it is low, refill as specified in the engine 

manufacturer’s maintenance instructions. The radiator 

should be filled to about 1 inch below the filler neck. 

FUEL PRESSURE TABLES

The following tables are the fuel pressure readings at each 

reference in the system.

Single low pressure regulator (LP vapor only)

Ref#

1

3

4

Unit off

Line PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Two regulator system (LP vapor only)

Ref#

1

2

3

4

Unit off

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Starting

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Natural gas

Ref#

2

3

4

Unit off

2 PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

NG/LP FUEL CONVERSION

This generator set was tested on both LP and NG at the 

factory. Ensure proper fuel configuration before operating. 

CAUTION: EQUIPMENT DAMAGE 

Do not make any fuel adjustments or governor adjustments 

until all pressure readings are in compliance with 

specification. 

These engine/generator sets are easy to convert between 

LP or NG. As the engine timing is controlled by the ECU on 

the engine you only need to tell it what fuel you want to 

operate on. A small rocker switch has been provide on the 

underside of the engine control cabinet for this purpose.

Opening the rocker switch will tell the ECU mounted on 

the engine that you are operating on NG Fuel. Closing the 

rocker switch will tell the ECU that the fuel being supplied is 

LP. The Advance Power Controller has an indicator light for 

LP. When this light is on, the engine is set-up for LP, when 

the LP light is out the engine is set up for NG. The ECU will 

then reprogram the engine to operate on the proper fuel.

Содержание PSS60-17

Страница 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Страница 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Страница 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Страница 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Страница 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Страница 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Страница 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Страница 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Страница 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Страница 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Страница 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Страница 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Страница 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Страница 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Страница 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Страница 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Страница 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Страница 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Страница 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: