background image

8

OPM-117/B

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough. The most 

common cause for inoperative systems is an inadequate 

or incorrect fuel pressure. Performance of the engine is in 

direct relation to the correctness of the fuel system. Shown 

below is a diagram of a typical LP vapor fuel installation. 

Notice the following tables give two different units of 

measuring fuel pressure. The first and most accurate is 

the use of a simple water manometer. A manometer is 

calibrated in inches of water column . The second is with a 

pressure gauge calibrated in ounces per square inch. 

Reference numbers 1 through 3 in the diagram above are 

system parts supplied by the customer. Reference number 4 

is on the generator.

The following diagram is of a natural gas (NG) installation.

Reference numbers 2 through 4 in the previous diagram 

are system parts supplied by the customer. Reference 

number 4 is on the generator.

 LP TANK SIZING

Tank Temperature

PSS60 Tank Size

PSS90 Tank Size

60° F (16° C)

500 Gallons

1000 Gallons

32° F (0° C)

1000 Gallons

1000 Gallons

0° F (18° C)

2000 Gallons

2000 Gallons

-20° F (-29° C)

5000 Gallons

5000 Gallons

LIQUID WITHDRAWAL SYSTEMS

When installing a unit equipped with the LP liquid 

withdrawal, a primary regulator is not required on the 

supply tank. The supply line is connected to a liquid 

withdrawal valve on the supply tank and runs directly to 

the fuellock strainer mounted on the engine generator 

set. Normally a 3/8 to 1/2 inch copper line is acceptable 

for this type of fuel installation. You must be sure that the 

valve you have connected to on the supply tank is in fact a 

liquid supply valve and has a drop tube inside the tank that 

is pulling fuel from the bottom of the supply tank. Before 

starting the unit, you must confirm that you have a good 

liquid supply at the unit. Engine generator sets equipped for 

liquid withdrawal will not run properly when supplied with 

vapor fuel.

NATURAL GAS (NG)

The primary regulator (fuel meter) on the building should 

deliver the correct volume and pressure to the generator 

set. This regulator must be sized to deliver the required 

BTU’s to the generator set and all other appliances in the 

building. If the primary regulator (fuel meter) is a high 

pressure regulator, then a low pressure regulator must be 

installed to bring the pressure down to 4-6 oz. (7-11 inches 

water column) of pressure. This low pressure regulator must 

be at least 10 feet from the engine generator set; any closer 

installation will require a larger line be installed to provide 

a fuel reservoir. If this is not done, the demand regulator 

on the unit and the pressure regulator in the fuel line will 

interfere with each other. This regulator must be sized to 

accommodate the demand of the generator set and any 

other appliance connected to it. See the following table for 

the correct size of pipe to be installed.

Feet*

Size of pipe

Up to 25 ft

1.25” pipe

Over 25 ft**

1.25” pipe

*Allow an additional 3 feet for each standard elbow. 

** Not recommended for the PSS60

DO NOT use ‘street ells’ (restrictive).

WARNING: PERSONAL DANGER  

Do not use galvanized pipe in fuel line runs. The galvanized 

coating can become eroded and flake off, causing possible 

obstructions in the regulator or fuel valve. The results could 

range from inoperative engine to hazardous fuel leaks.

CAUTION:

Be careful when sealing gas joints. Excessive sealing 

compound can be drawn into the solenoid, regulator or 

carburetor causing an engine malfunction.

Содержание PSS60-17

Страница 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Страница 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Страница 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Страница 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Страница 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Страница 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Страница 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Страница 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Страница 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Страница 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Страница 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Страница 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Страница 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Страница 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Страница 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Страница 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Страница 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Страница 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Страница 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: