OPM-117/B

The following table shows the minimum conductor sizes 

between the generator and the ATS, based on wire type 

and temperature rating. Wire has been derated 40° C 

ambient temperatures.

Wire Temperature Rating

Cu Conductor

Al Conductor

kW

Volts

PH Amp

75°C

90°C

75°C

90°C

60

120/240

1

250

300 

MCM

250 

MCM

500 

MCM

350 

MCM

60

120/208

3

200

4/0 AWG

3/0 

AWG

300 

MCM

250 

MCM

60

120/240

3

175

3/0 AWG

2/0 

AWG

250 

MCM

4/0 

AWG

60

277/480

3

90

#2 AWG

#3 AWG

1/0 

AWG

#2 

AWG

90

120/240

1

350

600 

MCM

500 

MCM

(NOTE 1)

600 

MCM

90

120/208

3

300

500 

MCM

350 

MCM

600 

MCM

500 

MCM

90

120/240

3

250

300 

MCM

250 

MCM

500 

MCM

350 

MCM

90

277/480

3

150

2/0 AWG

1/0 

AWG

4/0 

AWG

3/0 

AWG

Note 1 - Two 250 MCM may be used.

For additional information on wire sizing refer to table 310-
16 of the National Electrical Code ANSI/NFPA 70.

C - Ground Lug, These ground lugs are bonded to 
ground and are provided for you to connect your 
ground wire from the transfer switch to. The lugs on 
the 60kW will accommodate #1 AWG to 250 MCM and 
should be torqued to 250 in. lbs. The lugs on the 90kW 
will accommodate #1 AWG to 300 MCM and should be 
torqued to 250 in. lbs.

D. 120 Volt Terminal Block. These terminals are for shore 
power. For a power line with one lead, plug into either 
terminals, ensuring the jumper is still connected. To isolate 
two leads for use of two separate circuit breakers, the 
jumper must be removed.

WARNING: EQUIPMENT DAMAGE

When installing a three-phase 240 Volt system, be sure you 

know which lead is the high voltage “wild” leg (208 Volt to 

neutral). The generator normally carriers the high voltage 

on the G2 lead.

The load current carrying wires (L) and (T) must be sized 
to handle the maximum load current without excessive 
voltage drop. By code, the wire must be heavy enough to 
handle the full current rating of the mainline circuit breaker 
(or fuse) in the entrance (or sub-panel) protecting the 
contactor switch.

All wires should be installed in rigid or flexible conduit. 
(knockouts are provided in the control box).

AC ELECTRICAL 

CONNECTIONS

NOTICE:  

CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL 

FIELD WIRING CONNECTIONS TO TERMINAL OF A CLASS 

2 CIRCUIT.

WARNING:

A mainline circuit breaker has been provided inside the 

generator housing. During all wiring installation, make 

sure the breaker is in the off position and the generator 

operators switch is in the off position. 

A - Neutral Lugs, These neutral lugs are isolated from 

ground and provided for you to connect your neutral wire 

from the transfer switch. The lugs on the 60 kW will handle 

wire sizes #4 AWG to 300 MCM and should be torqued to 

250 in lbs. The lugs on the 90 kW will accommodate #1 

AWG to 600 MCM and should be torqued to 300 in lbs.

B - Generator Circuit Breaker, This circuit breaker provides 

overload protection for the generator. Your power feeds 

from the transfer switch will connect to the bottom lugs on 

the circuit breaker. The generator power feeds have already 

been wired into the upper lugs.

The table below gives you the circuit breaker size, lug wire 

sizes and torque specification. (see the actual breaker for 

additional information and restrictions)

kW

Volts

PH Amp

Wire Capability

Lug 

Torque

60

120/240

1

250

#1 AWG-600 

MCM

375 in lbs

60

120/208

3

200

#4 AWG-300 

MCM

250 in lbs

60

120/240

3

175

#4 AWG-300 

MCM

250 in lbs

60

277/480

3

90

#14 - #3/0 AWG 120 in lbs

90

120/240

1

350

#1 AWG-600 

MCM

375 in lbs

90

120/208

3

300

#1 AWG-600 

MCM

375 in lbs

90

120/240

3

250

#1 AWG-600 

MCM

375 in lbs

90

277/480

3

150

#14 - #30 AWG

120 in lbs

 A

 

C

 

B

 

D

PSS60 CB PANEL

A

 

C

 

B

 

D

PSS90 CB PANEL

Содержание PSS60-17

Страница 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Страница 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Страница 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Страница 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Страница 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Страница 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Страница 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Страница 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Страница 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Страница 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Страница 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Страница 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Страница 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Страница 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Страница 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Страница 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Страница 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Страница 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Страница 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: