L1, L2, & L3 POWER OUTPUT LUGS:

These lugs will handle wire sizes from #4 to 600 MCM and should be 

torqued to 22 ft. lbs. Two lugs per generator output leg are provided for 

your use. These lugs are isolated from the generator frame.

In the 120/240V 3-Ph configuration with the wild leg (208 line to 

neutral) is wired to the L2 position. ALSO NOTE THAT BECAUSE OF 

A CONFIGURATION PROBLEM, THE DEEP SEA CONTROLLER 

WILL SHOW THE WILD LEG ON L1 BUT IT IS WIRED TO THE L2 

POSITION.

WARNING: PERSONAL DANGER:

This unit is shipped with the neutral and ground unbonded. If the unit 

is to be used as a stand-alone generator, you must bond neutral and 

ground together either at this terminal block or somewhere in your 

system.

GROUNDING

A grounding lug has been provided on the engine generator set and 

the generator set must be properly grounded to good earth ground. 

Generally an 8 foot copper rod driven into the earth will provide a 

proper earth ground.

RECEPTACLE PANEL

A: 20 AMP CIRCUIT BREAKERS:

2-20 Amp circuit breakers provide circuit breaker protection for the 2-20

Amp GFCI 120V receptacles.

B: 20 AMP/120V GFCI RECEPTACLES:

These 2-20 Amp (NEMA 5-20) GFCI protected receptacles are 

powered only when the selector switch is in the 240 or 208V position. 

They are dead when the voltage selector switch is in the 480V position.

C: 50 AMP CIRCUIT BREAKERS:

2-50 Amp circuit breakers provide circuit breaker protection for the 2-50

Amp 120/240V twist lock receptacles.

A

C

B

D

E

A.C. ELECTRICAL CONNECTIONS

NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL 

FIELD WIRING CONNECTIONS TO TERMINALS OF A CLASS 2 

CIRCUIT

All wiring must be completed in accordance with the National Electric 

Code as well as any state and local codes.

You must pay particular attention to wire size requirement for 

the amperage of service you are dealing with. The table below 

provides you guidance on wire sizing based on both wire type and 

amperage. 

Wire amperages have been derated for 40° C ambient 

temperatures operation.

WARNING: 

Make sure the generator is disconnected from the battery to prevent 

accidental starting. 

This AC terminal block is covered by a lockable access cover. Access 

for routing the wires into the terminal block is provided via a small 

access door just to the left of the main control panel door. You will also 

find your convenience receptacles located behind this small door. All 

receptacles located here have their own circuit breaker for protection. 

NEUTRAL LUGS:

These lugs are isolated from ground and provided for you to connect 

your neutral wire from the transfer switch to the generator.

The 1200 Amp terminal block lugs on the 300-350kW will handle wire 

sizes #3/0 to 600 MCM and should be torqued to 28 ft. lbs. 

The 1000 Amp terminal block lugs on the 250kW will handle wire sizes 

#3/0 to 500 MCM and should be torqued to 28 ft. lbs. (Rated for 900 

Amp for AL)

GROUND LUG:

These ground lugs are bonded to ground and are provided for you 

to connect your ground wire from the transfer switch to. The lugs will 

accommodate #6 AWG to 300 MCM and should be torqued to 22 ft. lbs.

Two lugs are provided for your use. 

Содержание DX100F4

Страница 1: ...RT 5 9 6 216 5 9 51 6 5 37 21 7 25 1 7 0 12 3 57 180 5 6 5 37 21 9 2 1 1 1 7 1 5 725 8 6 5 0 66 0 5 5 77 5 7 2 7 7 867 6 67 6 3 67 9 81 76 1 5 211 7 2 7 7 50 1 2 6 77 5 5 5 7 9 03 286 1 167 7 2 1 1 51...

Страница 2: ...fully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in the manual d...

Страница 3: ...nal word is to be limited to the most extreme situations WARNING WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indica...

Страница 4: ...5 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 17 9 Quarts Cooling System 50 50 mix DX130F4 Generator Wattage 109 000 130 000 123 000 130 000 kVa 109 162 154 102 Volts 12...

Страница 5: ...120 240 277 480 Phase Three Three Three PF 80 80 80 Amps 1215 1051 526 CB Size 800 800 800 Hertz 60 60 60 Engine Model FPT C13 TTE3X 13L Starting System 24 Volt Muffler Standard Fuel Consumption full...

Страница 6: ...s phase Excitor Stator Resistance 18 0 ohms Excitor Rotor Resistance 0 068 ohms phase cycles set points and signal output capabilities are possible Consult factory for procedure and passwords NOTICE T...

Страница 7: ...t for any damage If any damage is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that yo...

Страница 8: ...ine wear and shorten its useful life COOLANT Before starting the engine check the coolant level in the radiator If it is low refill as specified in the engine manufacturer s maintenance instructions T...

Страница 9: ...d state The battery can be left on this mode indefinitely During this mode the green LED will be on constantly This charger is mounted under the customer connection on the control side of the generato...

Страница 10: ...eptacles A C B D E A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A CLASS 2 CIRCUIT All wiring must be completed in accordance...

Страница 11: ...110 Standards This feature meets the annunciations requirements in applications requiring NFPA 110 level one protection DC INTERCONNECTIONS TO THE ATS WARNING Be sure Engine Generator is in the OFF p...

Страница 12: ...RESET button pressed to reset the module The icon will be flashing in the display SELECTING THE CORRECT VOLTAGE A variety of three phase voltages are available from the three position selector switch...

Страница 13: ...come on Note There is no start delay in this mode of operation 2 Press and release the green START ENGINE button The DSE 7310 MKII will send a start signal to the ECU on the engine The engine ECU wil...

Страница 14: ...ning light Simply reset the ATS start over Once you have completed testing of the ATS be sure you ALWAYS leave the system in the standby mode unless servicing the unit For standby operation press the...

Страница 15: ...tween these to leads must be between 190 264 Center tapped on 480 Volt LED Indicator Light FITTING AND OPERATING 2006 3 TD_AS440 AVR_03 09_04_GB SUMMARY OF AVR CONTROLS CONTROL FUNCTION DIRECTION VOLT...

Страница 16: ...HHN THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 2...

Страница 17: ...17 OPM 115 REV A SELECTOR SWITCH WIRING DIAGRAM DX90 DX130...

Страница 18: ...18 OPM 115 REV A DX175...

Страница 19: ...19 OPM 115 REV A DX250...

Страница 20: ...20 OPM 115 REV A DX90F4 DX130F4 DSE 7310 MKII WIRING DIAGRAM...

Страница 21: ...57 67 57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9 5 4 88 4 2 22 17 02 8 7 50 1 2 803...

Страница 22: ...AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING DELTA...

Страница 23: ...23 OPM 115 REV A ENGINE WIRING HARNESS DX90F4 DX130F4 DX175F4 DX350F4...

Страница 24: ...or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warr...

Отзывы: