D.C. ELECTRICAL CONNECTIONS
All DC connections are completed on the terminal strip just below
the engine control. All DC connection must be separate conduit. You
cannot mix AC and DC leads at the same conduit.
CONNECTION BOX TERMINALS
Wire size requirements for each of the connections may vary but
terminal lugs should be used for all connections. Torque spec for
terminal lugs is 9 in. lbs.
A - Customer Remote Start CONNECTIONS TERMINALS. The two
remote start leads from the Automatic Transfer Switch are connected
to the two terminals marked Ground and Start. The wire in terminal
labeled Ground is Battery Negative and the wire in the terminal labeled
Start is your Remote Start lead. Closing these two leads together will
signal the DSE 7310 MKII to go into an autostart mode and start up the
engine generator.
Depending on the distance, 14 to 16 gauge stranded wire should be
used. It is suggested that these wires be labeled S1 and S23. The
terminal blocks are designed to use terminal lugs on all wires and the
screws should be torqued to 9.6 in. lbs.
Note: Any relay closure can be used to start and stop this generator. As
long as the contact stays closed the engine generator set will continue
D: 50 AMP 120/240V TWISTLOCK RECEPTACLES:
2-50 Amp receptacles are powered only when the selector switch is in
the 208 or 240V position. They are dead when the selector switch is in
the 480V position. These two receptacles are 4-wire 120/240V. (Mating
plug is a CS6365)
E: 15 AMP 120V REVERSE PLUG:
This plug is provided to power the block heater and battery charger
mounted inside the unit when the unit is used for standby. It also allows
battery charging during periods of long term storage.
WARNING:
A mainline circuit breaker has been provided inside the generator
housing. During all wiring installations, make sure the breaker is in the
OFF position and the generator operating switch is in the OFF position.
to run. Once the relay is opened the unit will shut down and remain in
the standby mode until the remote start relay is closed again.
B - ESTOP- & ESTOP+. Remote Emergency Stop terminals. These
two terminals are shipped with a jumper installed. If your application
requires the installation of a Remote Emergency Stop switch, remove
the jumper and wire your switch to these terminals. This unit will not
start and run without either the jumper installed or a remote N/C switch
installed.
C - Battery Charger Failure. Battery charger failure relay input from
remote battery charger to DSE7310 MKII controller.
D - Remote Display Panel Interface Terminals. These interface
terminals are pre-wired to allow for the connection of a remote display.
This display allows for the remote annunciation of alarms at a location
such as a nurses station or a control room. This display can be used to
meet the remote annunciation requirements of NFPA 110 Standards.
(This feature meets the annunciations requirements in applications
requiring NFPA 110 level one protection).
DC INTERCONNECTIONS TO THE ATS
WARNING:
Be sure Engine/Generator is in the OFF position before you make any
DC interconnections.
CAUTION:
Never run the AC and DC wiring in the same conduit.
ASCO 300 UL SWITCH
Your DC connection points in the ASCO 300 ATS terminals “14” and
“15”. Depending on the size of the switch, they are located in different
locations.
13
5060-00
60708-165
A - Customer Remote Start CONNECTIONS TERMINALS.
The
two remote start leads from the Automatic Transfer Switch are
connected to the two terminals marked GROUND & START. The
wire in terminal GROUND is Battery Negative and the wire in the
terminal labeled START is your Remote Start lead. Closing these
two leads together will signal the DSE 7310 to go into an auto-
start mode and start up the engine generator.
Depending on the distance, 14 to 16 gauge stranded wire
should be used. It is suggested that these wires be labeled S1
JURXQGDQG6VWDUW
The terminal blocks are designed to
use terminal lugs on all wires and the screws should be torqued
to 9.6 in. lbs.
1RWH$Q\UHOD\FORVXUHFDQEHXVHGWRVWDUWDQGVWRSWKLV
JHQHUDWRU$VORQJDVWKHFRQWDFWVWD\VFORVHGWKHHQJLQH
JHQHUDWRUVHWZLOOFRQWLQXHWRUXQ2QFHWKHUHOD\LVRSHQHG
WKHXQLWZLOOVKXWGRZQDQGUHPDLQLQWKHVWDQGE\PRGHXQWLO
WKHUHPRWHVWDUWUHOD\LVFORVHGDJDLQ
B - ESTOP- & ESTOP+.
Remote Emergency Stop terminals.
These two terminals are shipped with a jumper installed. If your
application requires the installation of a Remote Emergency
Stop switch, remove the jumper and wire your switch to these
terminals.
This unit will not start and run without either the
jumper installed or a remote N/C switch installed.
.
C. - Battery Charger Failure.
Battery charger failure relay input
from remote battery charger to DSE7310 controller.
D - Remote Display Panel Interface Terminals.
These
interface terminals are prewired to allow for the connection of a
remote display. This display allows for the remote annunciation
of alarms at a location such as a nurses station or a control
room. This display can used to meet the remote annunciation
requirements of NFPA 110 standards. (
This feature meets the
annunciation requirements in applications requiring NFPA110
level one protection.)
DC Interconnections to the
Automatic Transfer Switch
*************
***** WARNING *****
*************
%HVXUH(QJLQH*HQHUDWRULVLQWKH³2))´SRVLWLRQEHIRUH
you make any DC interconnections.
*******CAUTION******
1HYHUUXQWKH$&DQG'&ZLULQJLQWKHVDPHFRQGXLW
ASCO 185 UL SWITCH
<RXU'&FRQQHFWLRQSRLQWVLQWKH$6&2$76DUH
WHUPLQDOV³´DQG³RQWKHLQWHUIDFHWHUPLQDOEORFN
ASCO 300 UL SWITCH
Your DC connection points in the ASCO 300 ATS are terminals
³´DQG³´'HSHQGLQJRQWKHVL]HRIWKHVZLWFKWKH\DUH
located in different locations.
TB7
removable
terminal block
TB7–4, TB7–5, TB7–6
1 2 3 4 5 6 7 8 9
Figure 4. TB7 generator starting contact terminals.
Table A. Generator Start Connections
When the Utility fails
Terminals on Controller
contact closes
TB7–4 and TB7–5
contact opens
TB7–5 and TB7–6
Содержание DX100F4
Страница 17: ...17 OPM 115 REV A SELECTOR SWITCH WIRING DIAGRAM DX90 DX130...
Страница 18: ...18 OPM 115 REV A DX175...
Страница 19: ...19 OPM 115 REV A DX250...
Страница 20: ...20 OPM 115 REV A DX90F4 DX130F4 DSE 7310 MKII WIRING DIAGRAM...
Страница 23: ...23 OPM 115 REV A ENGINE WIRING HARNESS DX90F4 DX130F4 DX175F4 DX350F4...