INTRODUCTION

PRODUCT DESCRIPTION

This engine-generator set is designed for unattended remote start 

operation. It can be operated as part of a fully automatic standby power 

system or independently as a local start unit in a prime power system. 

The engine-generator set is fully tested at the factory prior to shipment 

to insure proper operation of each individual component as well as the 

total system’s performance and reliability.

The engine generator set consists of a multi-cylinder, liquid cooled 

engine nominally operating at 1800 rpm. The generator frequency 

regulation is maintained by the engine governor to /- 1.5 Hz 

(cps), from no load to rated load for standard mechanical governors 

and to /- .5 Hz or better for units equipped with an electronic 

governor. The generator is a single bearing, direct drive, rotating field 

design.  The generator is connected to the engine flywheel via flexible 

drive disks. Generator set is skid mounted with isolation mounts 

between the engine and base on all units.

A customer supplied 12 Volt battery is required to complete the 

installation, the DX250-350 are 24 Volt systems. Battery requirements 

are listed later under the battery installation section. 

Unit Orientation Note:

 All references used in this manual for unit 

familiarization, access and component locations on the Generator Set 

are oriented from a TOP (plan) VIEW with engine at the FRONT and 

generator to the REAR.

WINPOWER uses a common junction box for all customer control and 

power connections (both AC output and DC control). The common 

electrical junction box is always on the left side at the generator end of 

the machine.

The engine is controlled and Generator Set operation is monitored for 

safe operation by a programmable microprocessor based electronic 

Engine Control Module (ECM) with an LCD digital display. The 

generator set ECM control is mounted on a vertical pedestal on the 

right side of the generator. The ECM is programmed with a cycle 

cranking sequence - 3 cycles of 15 seconds on/15 seconds off, and 

5 minute cool-down delay. The cool-down delay can be changed in 

the field from 0 to 30 minutes by your installer. Other features, timing 

Stamford Newage Model# UCI274H (12 lead)

Voltage Regulator    

SX460

Rotor Resistance    

1.82 ohms

Stator Resistance    

0.0155 ohms/phase

Excitor Stator Resistance   20.0 ohms

Excitor Rotor Resistance   0.091 ohms/phase

Stamford Newage Model# HCI434D (12 lead)

Voltage Regulator    

MX341

Rotor Resistance    

1.05 ohms

Stator Resistance    

0.00124 ohms/phase

Excitor Stator Resistance   18.0 ohms

Excitor Rotor Resistance   0.068 ohms/phase

cycles, set points, and signal output capabilities are possible. Consult 

factory for procedure and passwords.

NOTICE:

These units will automatically transfer if a power outage occurs while 

running in exercise mode.

GENERATOR SET

Every WINCO generator set has its own unique identity data plate. 

This data plate identifies the complete unit model number, the system 

serial number, and has links to the individual components that form the 

generator set in our factory records. Several of the major components 

also have their own individual data plates providing additional 

information to document build data for warranty and replacement parts. 

ENGINE

Refer to the engine operators manual for more detailed operation and 

maintenance information.

CAUTION: EQUIPMENT DAMAGE:

Be sure to check the engine oil level frequently as specified in the 

engine manual.

The engine manufacturer has established an excellent worldwide 

engine service organization; engine service is available from a nearby 

authorized dealer or distributor. Go to the WINCO website for a list of 

engine dealers (http://wincogen.com/Engine_Support) or contact the 

WINCO Service Department.

The rated power of each engine-generator is limited by the 

temperature, altitude, and all other ambient conditions specified by 

the engine manufacturer. Engine power may decrease 3½% for each 

1000 feet above sea level, and will decrease an additional 1% for each 

10 degrees Fahrenheit above 60° Fahrenheit. Units should not be 

operated in ambient temperature greater than 125° Fahrenheit.

GENERATOR

WINCO generator sets use brushless, AVR (Auto-Voltage Regulator) 

controlled broad-range generator ends. The generator converts 

rotational mechanical energy into electrical energy. These WINCO units 

are equipped with generators manufactured by Cummins Generator 

Technology. Each generator ‘end’ has its own data tag. A unique serial 

number is on the data plate.

MODEL NUMBER STRUCTURE

The WINPOWER alpha-numerical numbering consists of a base model 

designation, followed by an options section, separated by a dash mark. 

The base component of the model numbering system identifies an 

engine type, engine starting method, fuel type, kilowatt rating, engine 

manufacturer, and number of generator poles. Following the separation 

dash mark is the voltage connection and optional installed equipment. 

Options include features like, weather enclosures (housing), base 

mounted fuel tank sizes, and trailer options. 

Please note that some features or packages, such as NFPA level I 

& II, do not have an indication place in this numbering system. They 

are issued and built with an M-Spec (i.e. M-10372) number which can 

Содержание DX100F4

Страница 1: ...RT 5 9 6 216 5 9 51 6 5 37 21 7 25 1 7 0 12 3 57 180 5 6 5 37 21 9 2 1 1 1 7 1 5 725 8 6 5 0 66 0 5 5 77 5 7 2 7 7 867 6 67 6 3 67 9 81 76 1 5 211 7 2 7 7 50 1 2 6 77 5 5 5 7 9 03 286 1 167 7 2 1 1 51...

Страница 2: ...fully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in the manual d...

Страница 3: ...nal word is to be limited to the most extreme situations WARNING WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indica...

Страница 4: ...5 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 17 9 Quarts Cooling System 50 50 mix DX130F4 Generator Wattage 109 000 130 000 123 000 130 000 kVa 109 162 154 102 Volts 12...

Страница 5: ...120 240 277 480 Phase Three Three Three PF 80 80 80 Amps 1215 1051 526 CB Size 800 800 800 Hertz 60 60 60 Engine Model FPT C13 TTE3X 13L Starting System 24 Volt Muffler Standard Fuel Consumption full...

Страница 6: ...s phase Excitor Stator Resistance 18 0 ohms Excitor Rotor Resistance 0 068 ohms phase cycles set points and signal output capabilities are possible Consult factory for procedure and passwords NOTICE T...

Страница 7: ...t for any damage If any damage is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that yo...

Страница 8: ...ine wear and shorten its useful life COOLANT Before starting the engine check the coolant level in the radiator If it is low refill as specified in the engine manufacturer s maintenance instructions T...

Страница 9: ...d state The battery can be left on this mode indefinitely During this mode the green LED will be on constantly This charger is mounted under the customer connection on the control side of the generato...

Страница 10: ...eptacles A C B D E A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A CLASS 2 CIRCUIT All wiring must be completed in accordance...

Страница 11: ...110 Standards This feature meets the annunciations requirements in applications requiring NFPA 110 level one protection DC INTERCONNECTIONS TO THE ATS WARNING Be sure Engine Generator is in the OFF p...

Страница 12: ...RESET button pressed to reset the module The icon will be flashing in the display SELECTING THE CORRECT VOLTAGE A variety of three phase voltages are available from the three position selector switch...

Страница 13: ...come on Note There is no start delay in this mode of operation 2 Press and release the green START ENGINE button The DSE 7310 MKII will send a start signal to the ECU on the engine The engine ECU wil...

Страница 14: ...ning light Simply reset the ATS start over Once you have completed testing of the ATS be sure you ALWAYS leave the system in the standby mode unless servicing the unit For standby operation press the...

Страница 15: ...tween these to leads must be between 190 264 Center tapped on 480 Volt LED Indicator Light FITTING AND OPERATING 2006 3 TD_AS440 AVR_03 09_04_GB SUMMARY OF AVR CONTROLS CONTROL FUNCTION DIRECTION VOLT...

Страница 16: ...HHN THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 2...

Страница 17: ...17 OPM 115 REV A SELECTOR SWITCH WIRING DIAGRAM DX90 DX130...

Страница 18: ...18 OPM 115 REV A DX175...

Страница 19: ...19 OPM 115 REV A DX250...

Страница 20: ...20 OPM 115 REV A DX90F4 DX130F4 DSE 7310 MKII WIRING DIAGRAM...

Страница 21: ...57 67 57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 4 25 46 53354 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 9 5 92 7 8670 17 5 267 7 9 5 4 88 4 2 22 17 02 8 7 50 1 2 803...

Страница 22: ...AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING DELTA...

Страница 23: ...23 OPM 115 REV A ENGINE WIRING HARNESS DX90F4 DX130F4 DX175F4 DX350F4...

Страница 24: ...or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warr...

Отзывы: