![Wilo Yonos GIGA-N 125-5,5 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/wilo/yonos-giga-n-125-5-5/yonos-giga-n-125-5-5_installation-and-operating-instructions-manual_983047032.webp)
en
Installation and electrical connection
32
WILO SE 2020-10
6.7.4
Terminals
Control terminals
A
U
X
SSM
SBM
E
xt
.
off
M
P
D
D
G
G
N
D
10
V
/20m
A
L
H
IN
2
G
N
D
IN
1
+
24V
Fig. 27: Control terminals
Please also see the following table “Terminal assignment”.
Power terminals (mains connection terminals)
L1
L2
L3
L1
L2
L3
5.5 ... 7.5 kW:
11 ... 22 kW:
1.5 ... 4 kW:
Fig. 28: Power terminals
Please also see the following table “Terminal assignment”.
Additional earthing
DANGER
Risk of fatal injury due to electrical current!
As motors from 11 kW generate more leakage current, improper electrical connec-
tions can lead to fatal electric shock!
• Motors from 11 kW must be additionally connected to a reinforced earth con-
nection.
Fig. 29: Additional earthing, from 11 kW motor power
Tightening torque
[Nm] ± 10 %
Control terminals
0.5
Power terminals
1.5 – 7.5 kW
11 – 22 kW
0.5
1.3
Содержание Yonos GIGA-N 125-5,5