Installation and electrical connection
en
Installation and operating instructions Wilo-Yonos GIGA-N
29
CAUTION
Risk of material damage caused by improper electrical connection!
Ensure that the current type and voltage of the mains connection correspond to the
specifications on the pump rating plate.
6.7.1
Fuse on mains side
Comply with the regulations of the local energy supply company!
Maximum permissible fuse protection, see following table; observe the rating plate
data!
Power P
N
Max. fuse [A]
1.5 ... 11 kW
25
15 kW
35
18.5 ... 22 kW
50
Table 8: Maximum permissible fuse protection
Circuit breaker
The use of a circuit breaker is recommended.
NOTICE
Circuit breaker trigger characteristic: B
Overload: 1.13 – 1.45 x I
nom
Short-circuit: 3 – 5 x I
nom
Residual-current device (RCD)
This pump is equipped with a frequency converter. This means it may not be protec-
ted by a residual-current device.
Frequency converters can impair the functioning of
residual current-operated protection circuits.
Exception:
residual-current devices which have a selective type B universal current-
sensitive design are allowed:
ƒ
Labelling:
ƒ
Trigger current
–
< 11 kW: > 30 mA
–
≥ 11 kW: > 300 mA
6.7.2
Electromagnetic compatibility
The IEC 61000-3-12 standard regulates the connection to the public low voltage sup-
ply network.
Pumps in efficiency classes 11 ... 22 kW are devices for professional use. They are sub-
ject to special connection conditions, as an R
SCE
of 33 at the connection point is insuffi-
cient to operate them. The pumps have been assessed based on table 4 of the standard
(“three-phase devices under special conditions”).
Pumps in efficiency classes 11 ... 22 kW only comply with the standard IEC
61000-3-12:2011 if the following condition is met at all public connection points:
ƒ
At the interface between the electrical installation of the user and the public power
supply network, the short-circuit power S
SC
must be greater than or equal to the val-
ues listed in the following table!
Motor power [kW]
Short-circuit power S
SC
[kVA]
11
≥ 1800
15
≥ 2400
18.5
≥ 3000
22
≥ 3500
Table 9: Required short-circuit power S