Installation and operating instructions Wilo-Control MS-L 1x4kW
31
INSTALLATION English
4.
Fix the switchgear using four screws (max. Ø:
4 mm) and appropriate anchors onto the wall.
5.3.3. Positioning of signal transmitters
For automatic control of the connected pump,
a corresponding level control device must be
installed. This needs to be provided by the cus-
tomer.
Float switches may be used as signal transmitters.
Connection of level sensors or electrodes is not
possible! The corresponding signal transmitters
must be installed according to the unit's installa-
tion plan.
DANGER - explosive atmosphere!
If the connected signal transmitters are used
in potentially explosive areas, there is a dan
-
ger of fatal injuries from explosions! The con
-
nected signal transmitters must always be
used outside of potentially explosive areas.
Installation must always be carried out by
a qualified electrician.
Note the following:
•
When using float switches, ensure that these can
move freely in the operating space (pump cham-
ber, reservoir).
• The water level of the connected pump must not
fall below the minimum.
•
The maximum switching frequency of the con
-
nected pump must not be exceeded.
5.4. Electrical connection
POTENTIALLY fatal danger due to electrical
voltage!
Incorrect electrical connections can cause fa-
tal electric shocks. Electrical connections may
only be carried out by a qualified electrician
approved by the local energy supply company,
in accordance with locally applicable regula-
tions.
DANGER - explosive atmosphere!
If the connected pump and signal transmitter
are used in potentially explosive areas, there
is a danger of fatal injuries from explosions!
The connected pump and signal transmitter
must always be used outside of potentially
explosive areas. Installation must always be
carried out by a qualified electrician.
NOTE
• Depending on the system's impedance and the
connected consumers' max. no. of connections/
hour, voltage fluctuations or voltage drops may
occur. Always have the electrical connections
carried out by an electrician authorised by the
local energy supply company.
• Observe the installation and operating in-
structions for the connected pump and signal
transmitters.
• The mains connection current and voltage must
be as stated on the rating plate.
• All-pole disconnecting, K-type circuit breakers
must be installed!
•
Max. fuse protection on mains side: 16 A
•
On switchgears without a power supply sepa
-
ration device (O version: without main switch or
plug) this must be provided by the customer!
•
It is recommended a residual-current-operated
protection switch (RCD, type A, sinus wave-form
current) be installed. Observe the local laws and
regulations on this too!
• Route the power supply cable in accordance with
the valid norms and regulations and according to
the wiring diagram.
• Ground the system (switchgear and all electric
consumers) in accordance with the regulations.
Fig. 2.: Overview of individual components
A Switchgear with main switch
W Switchgear with plug
C Switchgear without main switch and plug
1 Main switch
5 DIP switch
2 Motor contactor
6 Potentiometer for fol-
low-up time
3 Terminal strip
7 Rechargeable battery
installation location
4 Earth terminals
8 Mains terminal strip
5.4.1. Switchgear mains connection - with main
switch
Insert the cable ends of the power supply cable
laid on-site through the threaded cable connec-
tions and secure them accordingly.
Connect the wires
to the main switch
as follows:
•
Mains connection 1~230 V:
•
Cable: 3-core
•
Terminals: 4/T2 (L), N (N)
• The protective earth conductor (PE) is connect-
ed to the earth terminal (
;
).
•
DIP switch position "8": OFF (bottom position)
NOTE
To function correctly, 2 bridges (supplied) must
be installed on the mains terminal strip:
• Terminal 1 and 2
• Terminal 3 and 4
•
Mains connection 3~400 V:
•
Cable: 5-core
•
Terminals: 2/T1 (L1), 4/T2 (L2), 6/T3 (L3), N (N)
• The protective earth conductor (PE) is connect-
ed to the earth terminal (
;
).
•
DIP switch position "8": ON (top position)
• A
clockwise
rotating field must be present!
5.4.2. Switchgear mains connection - with plug ("S"
version)
Insert the plug into the socket:
•
Mains connection 1~230 V: Shock-proof socket
•
Mains connection 3~400 V: CEE socket (a
clock-
wise
rotating field must be present)
Содержание Wilo-Control MS-L
Страница 2: ...Fig 1 1 2 3 ...
Страница 6: ......
Страница 8: ......
Страница 24: ......
Страница 70: ......
Страница 86: ......
Страница 102: ...102 WILO SE 02 2018 V05 DIN A4 Portugués ANEXO Reserva se o direito de proceder a alterações técnicas ...
Страница 118: ......
Страница 206: ......
Страница 236: ......
Страница 282: ......
Страница 300: ......
Страница 316: ......