Object status
network output SNVT_obj_status nvoStatus
This output network variable provides status information on the individual
objects. The information is bit-coded. All bits are deleted after a reset.
Value range
File Directory Address
network output SNVT_address nvoFileDirectory
This network variable specifies the start address of the configuration file direc-
tory.
Additional information can be found in the LonMark documentation pertaining
to the node object.
Bit
Function
invalid_id
A non-existent object was addressed.
invalid_request
An unknown request was sent.
disabled
The object in concern is switched off.
electrical_fault
The pump controller object indicates an electrical error.
unable_to_measure
The pump controller object cannot communicate with the pump.
manual_control
The pump controller object is disabled for controlling by the
hardware settings at the pump (ext. off, ext. min, IR monitor)
in_alarm
The pump controller object indicates an error.
report_mask
Indicates that nvoStatus contains the status mask, i.e. the list of all
supported bits, due to a preceding RQ_REPORT_MASK request.