6.2.4 Value ranges and resolutions of the configuration output network variables
6.2.5 Description of the network variables
Object request
network input SNVT_obj_request nviRequest
This input network variable triggers various operations concerning the node and
object status. It consists of 2 bytes, the ID byte and the value byte. The ID byte
indicates the number of the object to which the request applies. The ID value 0
refers to the node object; in this case requests may also affect all other objects.
The ID value 1 refers to the pump-controller object.
Value range
Output
configuration
variable
Mandat./
optional
CPT / NVT
Object Number Value
nciDevMajVer
O
SCPTdevMajVer
0
165
03
nciDevMinVer
O
SCPTdevMinVer
0
166
00
nroPumpChar
M
SCPTpumpCharacteristic
1
233
depends on
pumptype
nciObjMajVer
O
SCPTobjMajVer
1
167
03
nciObjMinVer
O
SCPTobjMinVer
1
168
00
Value
Function with ID = 0
Function with ID = 1
RQ_NORMAL
Normal operation of all objects Normal operation of pump
controller
RQ_DISABLED
Stops all objects
Stops the pump controller
RQ_ENABLE
Enables the node object
Enables the pump controller
RQ_UPDATE_STATUS
Updates the node object status
(OR operation for all objects)
Updates the pump controller
status
RQ_REPORT_MASK
Supported node object status
signals (OR operation for all
objects)
Supported pump controller
status signals
RQ_CLEAR_STATUS
Deletes certain status signals in
all objects
Deletes certain pump
controller status signals
Содержание IF-module LON