WILO SE 05/2011
Remote pressure sensor minimum value
network input config nciRemMinPress
This optional input configuration network variable defines the lower limit value
of an external differential pressure sensor. This network variable is not currently
assigned any function.
Value range
-3276.8 – 3276.6 kPa (in 0.1 kPa steps). 3276.7 kPa is an invalid value.
Default value
<nciRemMinPress> = 3276.7 kPa
SCPT reference: SCPTminRemotePressureSetpoint (239)
Remote pressure sensor maximum value
network input config nciRemMaxPress
This optional input configuration network variable defines the upper limit value
of an external differential pressure sensor. This network variable has an
influence on the relative setpoint settings via nviPumpSetpoint and on the value
supplied by nvoPumpCapacity if the preset value is smaller than
nroPumpChar.pressMax. Larger values are always limited internally to
nroPumpChar.pressMax.
Value range
-3276.8 – 3276.6 kPa (in 0.1 kPa steps). 3276.7 kPa is an invalid value.
Default value
<nciRemMaxPress> = 3276.7 kPa
SCPT reference: SCPTmaxRemotePressureSetpoint (240)
Remote temperature sensor minimum value
network input config nciRemMinTemp
This optional input configuration network variable is currently not assigned to
any function.
Value range
-273.17 – 327.66 °C (in 0.01 °C steps). 327.67 °C is an invalid value.
Default value
<nciRemMinTemp> = 327.67 °C
SCPT reference: SCPTminRemoteTempSetpoint (243)