Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON
64
English
Maintenance states
network output SNVT_dev_maint nvoMaintenance
This optional output network variable provides bit-coded service information of
the pump.
Value range
service_required = service required
Transmission
This value is transmitted whenever a change is made.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Fluid temperature
network output SNVT_temp_p nvoFluidTemp
This optional output network variable provides the fluid temperature.
Value range
-273.17 – 327.66 °C (in 0.01 °C steps). 327.67 °C is an invalid value.
Transmission
This value is automatically transmitted if it deviates from the value transmitted
last by more than 5 °C.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Power consumption in watts
network output SNVT_power nvoPower
This optional output network variable provides the power consumption of the
pump or, in the event of double pumps, the total power output of the master
and slave.
Value range
0 – 6553,5 W (in 0,1 W steps).
Transmission
This value is automatically transmitted if it deviates from the value transmitted
last by more than 10% of the maximum power consumption of the pump.